On/Off 

Keep 

  key depressed for 3 seconds to switch between online and offline. 

Set (water) Temperature (SP) 

Press 

 

  key to set temperature. Keep depressed can fast set. Factory default set is 40

System Parameter Set 

Keep 

 

depressed for 3 seconds, the big digits show “P00” for password entering. 

Press 

 

  key to set password, press 

  to confirm. 

If the password is wrong, exit. Else enter into parameter set status: 

Press 

 

  to select parameter. Press 

  to show the value of the parameter. 

Press 

 

  to set the value. Press 

  to return back to parameter selection. 

Keep 

  depressed for 3 seconds to save the settings, and exit. 

The status will exit, if there is no key operation for 15 seconds, and the settings will not be saved. 

System Parameter Table: 

No. 

Code 

Setting function 

Range 

Indication 

Default 

U01 

Hysteresis 

2

 ~ 

10

 

 

U30 

Defrost start time 

10

 ~ 

90 min 

 

45 

U31 

Defrost start temperature 

-9

 ~ 

0

 

 

-5 

U32 

Defrost stop temperature 

2

 ~ 

30

 

 

10 

U33 

Maximum defrost time 

2

 ~ 

15 min 

 

U34 

Valve mode 

0

 ~ 

0: heat off, defrost on 
1: heat on, defrost off 

U50 

Exhaust protection temperature 

50

 ~ 

125

 

 

110 

U51 

High/low pressure warning mode 

0

 ~ 

0: Disable 
1: Closed when warning 
2: Open when warning 

U52 

Water flowing switch mode 

0

 ~ 

0: Disable 
1: Effective when closed 
2: Effective when open 

10 

U80 

Auto restart function 

0

 ~ 

0: Disable; 1: Enable 

11 

U81 

Keypad lock 

0

 ~ 

0: Unlocked; 1: Locked 

12 

U90 

passwords 

00

 ~ 

99 

 

11 

Working Mode 

Press 

 

to switch between “AUTO” and “SAVE” working mode. 

“AUTO” mode: always heating according setting. 
“SAVE” mode: only heating within three set periods. 

When “Auto restart function” is disabled, it will be “AUTO” mode after power supplied. 

Clock Setting 

Press 

  key, the hour digits will blink, press 

 

  key to set hour. 

Press 

  key again, minute digits will blink, press 

 

  key to set minute. 

Press 

  key to exit. 

Periods Setting for “SAVE” Mode 

Keep 

  key depressed for 3 seconds to enter the period setting.   

Press 

  key to select the period and on/off. Press 

 

  to set the value of the time. 

Keep 

  key depressed for 3 seconds to save the settings, and exit. 

The status will exit, if there is no key operation for 15 seconds, and the settings will not be saved. 

The maximum periods are 3. Every period has a on-time and a off-time. 

If one 

period’s on-time = off-time = 0, this period will be shut off. 

If one period’s off-time is earlier than its on-time, this off-time is the time of the 2

nd

 day. 

Keypad Lock 

When U81 = 1, only 

  and 

  have reaction. 

Summary of Contents for ZL-R200A

Page 1: ...mpressor 15A Heating 8A Others 3A Failure Code No Code Failure No Code Failure 1 E01 Water container sensor failure 5 E05 Water flow warning 2 E02 Pipe Coil sensor failure 6 E06 High low pressure input warning 3 E03 Exhaustion sensor failure 7 E07 Data saving failure 4 E04 Outdoor sensor failure 8 E08 Communication failure Display Indication Icon Display Not shown Icon Displaying Not shown Online ...

Page 2: ...High low pressure warning mode 0 2 0 Disable 1 Closed when warning 2 Open when warning 0 9 U52 Water flowing switch mode 0 2 0 Disable 1 Effective when closed 2 Effective when open 0 10 U80 Auto restart function 0 1 0 Disable 1 Enable 0 11 U81 Keypad lock 0 1 0 Unlocked 1 Locked 0 12 U90 passwords 00 99 11 Working Mode Press to switch between AUTO and SAVE working mode AUTO mode always heating acc...

Page 3: ...pressor and outdoor fan stop 55 seconds later valve acts 5 seconds later start compressor Stop defrosting When T pip U32 or the compressor has been running for U33 stop defrosting Stop compressor 55 seconds later valve acts 5 seconds later start heating control Defrost after turning the system online When turn online if the T pipe U31 defrost 1st Timer Defrost If pipe sensor fails and the compress...

Page 4: ...tly otherwise system does not work correctly The real clock can only keep running correctly for 72 hours after power supply loses All sensors must be installed at correct position Do not plug in out panel bundle with power supplied Panel should be installed indoors instead of outdoors ...

Reviews: