Alarming code 

Code 

Remark 

E1 

Water sensor failure 

E2 

Defrost sensor failure 

E3 

External alarming (all controller outputs will be de-energized) 

 

Operation 

Set setpoint 

Enter into temperature setting status: Keep

SET

depressed for 3 seconds. 

The SET lamp will be on. The current setpoint displays. 

Press

or

to set setpoint. (keep the keys depressed can fast setting) 

Keep

SET

depressed for 3 seconds, exit the setting status, the setting will 

be saved.

 

The setting status will exit, the set value will

 not be saved,

 if there is no key operation for 10 seconds. 

Set parameter 

Enter into parameter setting status: Successively and fast press

, like input password. 

The SET lamp will be blinking. The 1

st

 

parameter code “F01” displays. 

Press

or

to select code (F01, F02, F03, 

…). 

Press 

SET

  to display the value of the code. 

Press

or

to set the value of the code. (keep the keys depressed can fast setting) 

Press

SET

to return to parameter code display. 

By this, all code could be set. 

Keep

SET

depressed for 3 seconds, exit the setting status, the settings will 

be saved.

 

The setting status will exit, the set values will 

not be saved

, if there is no key operation for 30 seconds. 

Check pipe temperature 

In online status, short press

  will blinkingly show pipe temperature for 10 seconds. 

Short press

  could stop show the pipe temperature.

 

Parameter code table 

Code 

Function 

Setting range 

Remark 

Factory 

set 

F01 

Temperature control mode 

0/1 

0: constant temperature   
1: cooling only 

F02 

Heating mode 

0/1 

0: by compressor   
1: by electrical heater 

F03 

Hysteresis 

0.1 ~ 20.0

 

 

1.0 

F04 

Calibration for water sensor 

-9.9 ~ 9.9

 

 

0.0 

F05 

Calibration for pipe sensor 

-9.9 ~ 9.9

 

 

0.0 

F06 

Delay protection for compressor 

0 ~ 10 min 

 

F07 

Temperature for start defrost 

-20 ~ 20

 

 

-5 

F08 

Temperature for stop defrost 

-20 ~ 20

 

If F08 

≤ F07, disable defrost function 

10 

F09 

Max defrost time 

0 ~ 60 min 

 

F10 

Min time to start defrost 

(1)

 

0 ~ 600 min 

0: disable defrost function 

30 

F11 

Buzzing alarm 

(2)

 

0/1 

0: disable   
1: enable 

F12 

External alarm setting 

0 ~ 2 

0: disable 
1: Effective when short 
2: Effective when open 

F13 

Delay for external alarm 

0 ~ 120 sec 

 

Note: (1) The continuous energized time for compressor. (2) When alarming buzzing, it could stop by press any key. 

 

Control 

On/Offline control 

Keep

depressed for 3 seconds to switch between online and offline. 

Cooling only mode (F01 = 1) 

If (water temperature) 

≥ (se F03), and the compressor has stopped for F06, the compressor energized. 

If (water temperature) 

≤ (setpoint), the compressor de-energized. 

Control sequence: Compressor on, fan will be on after 10 seconds. Compressor off, fan will be off after 5 seconds. 

Summary of Contents for ZL-807A

Page 1: ...2 0 4 Heat by electrical heater F02 1 4 Defrost F02 0 and under heating mode 4 Forced defrost F02 0 under heating mode 4 Fast launch Force the compressor energized 4 Pump control 4 External alarm input 4 Delay protection for compressor 4 Auto restart 4 Calibration 4 Waring for sensor failure 4 Restore to factory settings 5 Wiring diagram 5 Diagram one heating by compressor 5 Diagram two heating by...

Page 2: ...With 2 sensors we can check outdoor pipe temperature Water pump on off control Compressor delay protection Instant start compressor Temperature calibration Sensor failure warning External warning input Auto restart for power supply failure Specification Power supply 100 240Vac 50 60Hz Outputs Compressor 40A 250Vac relay can drive 2HP compressor Valve Heater 5A 250Vac resistance Fan 5A 250Vac resis...

Page 3: ...erature In online status short press will blinkingly show pipe temperature for 10 seconds Short press could stop show the pipe temperature Parameter code table Code Function Setting range Remark Factory set F01 Temperature control mode 0 1 0 constant temperature 1 cooling only 0 F02 Heating mode 0 1 0 by compressor 1 by electrical heater 0 F03 Hysteresis 0 1 20 0 1 0 F04 Calibration for water sens...

Page 4: ... seconds start compressor heating after 30 seconds Fan stops during defrosting Forced defrost F02 0 under heating mode Keep and depressed simultaneously for one second to enter into forced defrosting Forced defrosting works the same way as periodical defrost Once launched forced defrost it will not stop till the full process finished Fan stops during forced defrosting Fast launch Force the compres...

Page 5: ...Pages Restore to factory settings Keep SET and depressed simultaneously for 2 seconds display UnL Press twice all settings will restore to factory default values Wiring diagram Diagram one heating by compressor Diagram two heating by heater ...

Page 6: ...ages Dimension Case size Embedded hole If the cable protection rubbers could be removed during installation Hole size 136 1 86 5 mm R 7 mm If the cable protection rubbers could not be removed during installation Hole size 135 1 90 5 mm R 6 mm ...