3rd
temperature
21
U63
Upper limit humidity
0
~
100 %
100
22
U64
Lower limit humidity
0
~
100 %
0
23
U99
Passwords
0000 ~ 9999
0000
:
no passwords
0000
Control function instruction
Temperature control
Cooling control:
◇
When the temperature≥
【
setting temp.
】
+
【
temperature difference
】
,and temperature load (R3) stop time meet
【
temp. load
delay protection
】
,temp. Load on;
◇
When the temperature≤
【
setting temp.
】
,temp. Load (R3) off;
Heating control:
◇
When the temperature≤
【
setting temp.
】
-
【
temperature difference
】
,and temperature load stop time meet
【
temp. Load delay
protection
】
, temp. Load (R3) on;
◇
when the temperature≥
【
setting temp.
】
, temp. Load (R3) off.
Humidity control
Dehumidifition control
◇
when humidity ≥
【
setting humidity
】
+
【
humidity difference
】
, and humidity load (R2) stop time meet
【
humidity delay load
protection
】
, humidity load on
;
◇
when humidity ≤
【
setting humidity
】
, humidity load (R2) off
Humidification control
:
◇
When humidity ≤
【
setting humidity
】
-
【
humidity difference
】
, and humidity load (R2) stop time meet
【
humidity delay load
protection
】
, humidity load (R2) on
;
◇
when humidity≥
【
setting humidity
】
, humidity load (R2) off
Dewing warning
When humidity get to dewpoint, after
【
dewing warning delay
】
controller enter dewing warning state. If
【
dewing warning way
】
is C, digital shows”E2” alarm, humidity load output stop, warning output (R1) on. If
【
dewing warning way
】
is V, digital
shows”99.9%”alarm, still output.
Timed control
Timing circle control:
◇
When enter timing load 1 timing 1, timing load 1(R5) on, timing load 2 (R4) off.
◇
When enter timing load 1 timing 2, timing load 2 (R4) on, timing load 1 (R5) off.
◇
When enter timing on 2, timing load 3(R1) on.
◇
When enter timing off 2, timing load 3(R1) off.
Load delay protection
◇
Controller power is on, all load output (R2 R3) run after load delay protection
;
◇
Running process, the temperature and humidity load (R2 R3) after downtime must be after load protection delay to start
again.
U
pper temperature and humisity limit protection
◇
U60=3, R1 is timing relay. When temperature or humidity beyond the limit, R1 turn on, R2 R3 off, R4 R5 still the same
◇
U60=2, R1 is timing function. When humidity or temperature beyond limit R1 turn on.
◇
U60=1, R1 is timing function, limit protecting function stop.
Sensor
◇
When the sensor broken controller shows”E1”, humidity and temperature load off, warning output on.