IF52
9.5 Linearisation settings in %
P01 (x) … P16 (y)
Linearisation registers and further information are available in section “10.2.3
Free programmable linearisation“ on page 54.
9.6 Set-up settings
Direction
This parameter changes the internal direction of counting (0 or 1), provided the
unit operates in the ROUND LOOP mode. See
Parallel inversion
When you change the value in this register from 0 to 1, data in the parallel
output will be inverted.
Parallel value
The numerical value set next to this item appears directly at the parallel output,
provided that the
register has been set to a value greater than 2
previously. The serial access code of the
setting can be changed at any time via serial network. This function may be
useful for testing the operation and wiring of the parallel output.
9.7 RS-232 settings
Unit Number
You can choose any serial address number between 11 and 99.
Default factory setting = 11
The address must not contain any “0“ because such numbers are reserved for
collective addressing.
Serial Baud Rate
Setting
Baud
0 (factory default)
9,600
1
4,800
2
2,400
3
1,200
4
600
5
19,200
6
38,400
MAN IF52 I_E 1.1.odt
9 - Parameter settings
50 / 60