11.2 General settings
Direction
This register is used to reverse the polarity of the analogue output signal when
converting quadrature A/B input signals or when A=impulse and B=direction.
0
=
no inversion of polarity
1
=
inversion of polarity
A/B Mode
This register sets the counting mode when two independent single-channel
inputs are provided:
0
= no combination
1
= sum A + B
2
= difference A – B
See DIL switch settings in the section “
6.1 Basic mode of operation and power-
” on page
Linearisation Mode
This register sets the linearisation mode.
0
Linearisation OFF, registers from
P1
to
P16
do not affect the output
characteristics.
1
Linearisation in the range 0 – 100%.
2
Linearisation over the full range –100% to +100%.
See examples in the section “12 – Scaling and linearisation functions“ on page
69.
Edge Mode
When quadrature A/B input is enabled (see section “6.1 Basic mode of operation
and power-down memory setting” on page 49), this setting allows simple count
(x1) or full quadrature count (x4), by accepting either rising edges from input A
only, or all rising and falling edges from inputs A and B.
0
= simple count (x1)
1
= quadrature count (x4)