EM58 – HS58 - HM58 MODBUS TCP/IP
registers in compliance with the
following relation:
Transmitted position =
Counts per revolution [101-102]
*
Real position
≤
Singleturn resolution [113-114]
NOTE
is currently enabled,
input registers, see on page 69.
WARNING
Every time you enable/disable the scaling function and/or
change the scaling values (see the
then you are required to set a new preset value (see the
registers) and finally save the new
function).
Code sequence
bit 1
It defines whether the position value output by the encoder
increases (count up information) when the encoder shaft
rotates clockwise (0 = CW) or counter-clockwise (1 = CCW).
If the bit 1
= 0, the absolute position value
increases
when the encoder shaft rotates
clockwise
; on
position value
increases
when the encoder shaft rotates
counter-clockwise
. CW and CCW rotations are viewed
from the shaft end.
WARNING
Changing this value causes also the position calculated by
the controller to be necessarily affected. Therefore it is
mandatory to execute a new preset (see the
registers) and save the parameters after setting
this item.
NOTE
input registers, see on page 69.
bits 2 … 7
Not used.
Bytes 1 ... 3
Not used.
MAN EM58_HS58_HM58 MT E 1.1.odt
Programming parameters
59 of 104
Summary of Contents for EMC58 MT
Page 101: ...This page intentionally left blank ...
Page 102: ...This page intentionally left blank ...