SFA-5000 • SFA-10000 Profibus
The following table shows the maximum transmission rates in relation to
permissible line length:
Baud rate [Kbit/s]
9.6
19.2
93.75
187.5
500
1500
12000
Max. cable length
1200 m
4000 ft
1200 m
4000 ft
1200 m
4000 ft
1000 m
3300 ft
400 m
1300 ft
200 m
660 ft
100 m
330 ft
4.9 RT Bus termination (Figure 3 and Figure 4)
WARNING
Power supply must be turned off before performing this operation!
A bus termination resistance is provided inside the encoder enclosure and has to
be activated as line termination if the encoder is at the ends of the transmission
line (i.e. it is either the first or the last device in the transmission line).
Use RT Switch to activate or deactivate the bus termination.
RT
Description
1 = 2 = ON
Activated: if the encoder is the first or the last
device in the transmission line
1 = 2 = OFF
Deactivated: if the encoder is not the first or the
last device in the transmission line
MAN SFA_5000_10000_PB E 1.0
Electrical connection
32 of 72