LIGHTSAFE ERLEDB Quick Start Manual Download Page 2

Lightsafe_ERLEDB_Instructions_Rev01 

MAINTAINED 

Permanent mains supply (L, N, E), lamp normally on automatic charge (LED ‘on’) (powered by mains supply), when the 

supply to L1 is switched on.  Permanent supply removed lamp on (powered by battery pack) charge LED off. 

Technical Specification: 

Voltage:    

                       

230v AC 50Hz 

Lamp:

 

8 pcs SMT5730 LEDs 

Wattage:   

        

6W  

Colour Temp:

 

6500K

 

Lumen Output Mains:

  

300lm

  

Battery:

 

3.6V 800mAh Ni-Cd 

Class:  

 

1  

Max Cable Size:

 

2 x 1.5mm² 

Emergency Duration:

  

3 Hours  

Weight:

 

525g 

Recharge Time:

 

24 hours  

Dimensions:

  

352x110x65mm 

Temp Range:

 

0˚C - 40˚C  

IP:               

 

IP65

 

 

 

TESTING  

Ensure the luminaires are tested in accordance with 5266-8 / BS EN 50172 

 

Daily:

   

Ensure the green charge LED is illuminated on each luminaire 

Monthly:

   Simulate a mains power supply failure for a period of time sufficient to ensure that each lamp is illuminated 

and then recorded in the log book 

Annually:

  Similar test to a monthly but the full emergency duration of the luminaire should be tested 

Defects:

  Any defects should be noted and recorded in the log book and actioned by a competent person as soon as 

possible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Warranty:

 

This product is covered by an extended warranty for 2 years from date of purchase. 
Batteries are regarded as a consumable item, and as such, are not covered by the Extended Warranty periods and are only covered 
by a 1 year warranty. 
The extended warranty is available following installation in the UK or Ireland by a competent person in accordance with the current 
building and IEE wiring regulations. 
For full terms and conditions in regards to our extended warranty please refer to the website. 

Environment: 

Please DO NOT dispose of electrical items or packaging as unsorted waste, use the recycling facilities provided by your local 

authorities. 

Due to our policy of continuous improvement we reserve the right to change specification without prior notice. 

Errors and omissions excepted. These instructions have been carefully checked prior to publication. However, no responsibility can 

be accepted by Firesafe for any misinterpretation of these instructions. 

 

LIGHTSAFE 

Distributed by: FIRESAFE

 

10 Sandersons Way, 

Blackpool, FY4 4NB 

Email: 

[email protected]

 

Web: www.firesafe.co.uk

 

 

Part No:
Date:
Date:

Signed

Date

Signed

Date

Signed

Date

Signed

Date

1

Short

2

Short 

3

Short 

4

Short 

5

Short 

6

Short 

7

Short 

8

Short 

9

Short 

10

Short 

11

Short 

12

Full Duraiton

INSTALLATION / TEST 

RECORDS

Location:
Installed By
Comissioned By:

FOURTH YEAR

MONTH

TEST

FIRST YEAR

SECOND YEAR

THIRD YEAR

 

Reviews: