Permanent mains supply (L, N, E), lamp normally on automatic charge (LED ‘on’) (powered by mains supply), when the
supply to L1 is switched on. Permanent supply removed lamp on (powered by battery pack) charge LED off.
Technical Specification:
Voltage:
230v AC 50Hz
Lamp:
8 pcs SMT5730 LEDs
Wattage:
6W
Colour Temp:
6500K
Lumen Output Mains:
300lm
Battery:
3.6V 800mAh Ni-Cd
Class:
1
Max Cable Size:
2 x 1.5mm²
Emergency Duration:
3 Hours
Weight:
525g
Recharge Time:
24 hours
Dimensions:
352x110x65mm
Temp Range:
0˚C - 40˚C
IP:
IP65
TESTING
Ensure the luminaires are tested in accordance with 5266-8 / BS EN 50172
Daily:
Ensure the green charge LED is illuminated on each luminaire
Monthly:
Simulate a mains power supply failure for a period of time sufficient to ensure that each lamp is illuminated
and then recorded in the log book
Annually:
Similar test to a monthly but the full emergency duration of the luminaire should be tested
Defects:
Any defects should be noted and recorded in the log book and actioned by a competent person as soon as
possible
Warranty:
This product is covered by an extended warranty for 2 years from date of purchase.
Batteries are regarded as a consumable item, and as such, are not covered by the Extended Warranty periods and are only covered
by a 1 year warranty.
The extended warranty is available following installation in the UK or Ireland by a competent person in accordance with the current
building and IEE wiring regulations.
For full terms and conditions in regards to our extended warranty please refer to the website.
Environment:
Please DO NOT dispose of electrical items or packaging as unsorted waste, use the recycling facilities provided by your local
authorities.
Due to our policy of continuous improvement we reserve the right to change specification without prior notice.
Errors and omissions excepted. These instructions have been carefully checked prior to publication. However, no responsibility can
be accepted by Firesafe for any misinterpretation of these instructions.
LIGHTSAFE
Distributed by: FIRESAFE
10 Sandersons Way,
Blackpool, FY4 4NB
Email:
Web: www.firesafe.co.uk
Part No:
Date:
Date:
Signed
Date
Signed
Date
Signed
Date
Signed
Date
1
Short
2
Short
3
Short
4
Short
5
Short
6
Short
7
Short
8
Short
9
Short
10
Short
11
Short
12
Full Duraiton
INSTALLATION / TEST
RECORDS
Location:
Installed By
Comissioned By:
FOURTH YEAR
MONTH
TEST
FIRST YEAR
SECOND YEAR
THIRD YEAR