Specplus
SPS2GFSVA32U or 317
Page 2 of 2
2' x 2' Recessed Fluorescent, Lens Frame Troffer
Static, 2 or 3 Lamp T8, 1-5/8"U or 2' Lamp
Ordering Information
Explanation of Catalog Number. Example: SPS2GFSVA32UUNVH3
Options/Accessories
Special Lenses
: Substitute
VY
for
VA
(standard) = .125" nominal pattern 12 with 7.8 oz. average weight
per square foot. Substitute
VI
for
VA
(standard) = .125" nominal pattern 12 with 6.8 oz. average weight per
square foot. Substitute
S1
or
S2
for
VA
(standard) = Sky Acrylic Lens (see Sky Lens sell sheet for
further details).
Plaster Frame
: Catalog Number:
PF22
.
Continuous Row Installation
: For F type fixtures, half width flanges are required between
fixtures. Order Catalog Number:
2FC TRIM CSP
(each joint).
Radio Interference Filter
: To order one RIF per fixture; SUFFIX:
R
.
To order one RIF per ballast; SUFFIX:
B
.
Fusing
: Internal fast-blow fusing. SUFFIX
A
.
Internal slow-blow fusing. SUFFIX
C
.
Electrical Wiring Options
: Consult factory.
Drywall Kit
: Order Catalog Number:
FK92X2
. (Request Folio OA30-10 Rev. A).
Chicago Plenum
: SUFFIX:
C
.
Specifications
Performance
: In an installation of 3 lamp 31W luminaires in a room cavity ratio of 1, reflectance
80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .72. To prevent glare the VCP shall
be not less than 35 either lengthwise or crosswise (at 100fc level) and the average brightness at 65°
shall not exceed 3497 candelas per square meter. To control veiling reflections, luminaire output in
the 30°-90° zone shall not be less than 66.8%.
Specifications (continued)
Materials
:
Chassis parts
are die-formed code gauge cold rolled steel. Housing with side rails hemmed
over and housing ends turned-in for safe handling.
Finish
:
Chassis exterior
–black baked polyester enamel.
Cavity
–white baked polyester enamel
minimum 86% reflectance. Phosphate undercoating.
Lenses
:
VA
(standard) extruded virgin acrylic, 3/16" square based female cones, running 45° to the
panel edge, .095" nominal thickness (similar to pattern 12).
VY
(optional) .125" nominal pattern 12
with 7.8 oz. average weight per square foot.
VI
(optional) .125" nominal pattern 12 with 6.8 oz. aver-
age weight per square foot.
Electrical
: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of
ballast, use wire suitable for at least 90°.
Labels
: I.B.E.W. UL and ULc Listed.
This product may have a mercury containing lamp.
Manage in accord with Disposal Laws. See: www.lamprecycle.org
Specplus:
Recessed
fluorescent
troffer
S
Static
2
Fixture
Width
Lens Frame:
FS
= Flat steel
frame.
RA
= Regressed
aluminum
frame.
FA
= Flat aluminum
frame.
Lens Shielding
Type:
VA
=Virgin acrylic
(standard)
S1
=Sky lens 1
S2
=Sky lens 2
See options and
consult factory
Lamp
Quantity
2
=2 Lamp
3
=3 Lamp
Ballast Type:
<
20THD
<
10THD
1 & 2 Lamp Elec. T8
SO *
H
I
*
1–3 Lamp Elec. T8
O3 *
H3 *
LOL T8 Dimming
PS
–
*Instant Start Standard
Other dimming options. Consult factory.
NOTE:
For
T8 UNV
, you must use
H
I
,
H3
Ballast Code.
Options:
Add appropriate suffix
to catalog no., ie: (A)
Voltage:
120, 277 or
UNV
=120-277
Lamp Type/
Fixture Length:
2U
=T8, 1-5/8"U Lamp
17
=T8, 2' Lamp
(Nominal 24")
Note:
For
Linear
T5 Lamp
option,
consult factory
SP
Standard Specplus Plus
SX
For NYC Code – Local 3 Manufactured
Ceiling Type:
G
= Grid
(lay-in T bar)
F
= Flanged (over
lap) Z spline and
plaster frame
0.0
45.0
90.0
FLUX
0
2391
2391
2391
5
2376
2376
2382
226
15
2269
2289
2315
647
25
2056
2106
2160
971
35
1728
1799
1877
1126
45
1277
1361
1467
1051
55
786
840
909
755
65
434
411
460
434
75
219
201
264
244
85
82
87
109
98
90
0
0
0
Model No. SPS2GFSVA32U12003
LER = FP - 64.1
IW - 76.2
BF - 0.88
Comparative yearly lighting energy cost per
1000 lumens = $3.74
Report Number: G00057
Catalog Number: SPS2GFSVA32U12003
Lamps: (3) U6T8
Luminaire: 2' x 2' SpecPlus with regressed
aluminum door frame and extruded
virgin acrylic shielding .095" nominal
thickness (similar to pattern 12).
Ballast: REL-3P32-SC
Report is based on 2725 Lumens per lamp.
Efficiency: 67.9%
CIE Type-Direct-Indirect
Plane:
0-Deg
90-Deg
Spacing Criteria:
1.2
1.3
Shielding Angles:
90
90
Plane:
0-Deg
90-Deg
Luminous Length:
21.875
21.875
CANDELA DISTRIBUTION
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG.
0-DEG.
45-DEG.
90-DEG.
45
5803.
6184.
6666.
55
4403.
4705.
5092.
65
3300.
3125.
3497.
75
2719.
2495.
3277.
85
3023.
3207.
4018.
LUMINANCE DATA IN CANDELA/SQ. METER
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
RC
80
50
30
RW 70 50 30 50 30 10 50 30 10
0
1 75 72 69 67 65 63 65 63 62
0
2 69 63 59 60 57 54 58 55 53
0
3 63 56 51 53 49 46 52 48 45
0
4 58 51 45 48 44 40 46 43 39
0
5 54 46 40 43 39 35 42 38 35
0
6 50 41 36 39 35 31 38 34 31
0
7 46 38 32 36 31 28 35 31 28
0
8 43 34 29 33 28 25 32 28 25
0
9 40 32 26 31 26 23 30 26 23
10 38 29 24 28 24 21 28 24 21
ZONE
LUMENS % LAMP
% FIXT
0
0-
0
30
1844
22.6
33.2
0
0-
0
40
2970
36.3
53.5
0
0-
0
60
4776
58.4
86.0
0
0-
0
90
5552
67.9
100.0
90-180
000
0
0.0
00
0.0
0
0-180
5552
67.9
100.0
ZONAL LUMEN SUMMARY
Job Information
Type:
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595
02/10
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group
Section 1A/Folio E60-24 Rev. B
Photometry
Sky Lens Options
S1