For Continuous Row Mounting – 6-1/2" wide, 12 Cell (1 Row) Parabolic Louver,

Static, 2 Lamp T8, IES RP1 For VDT

Lightolier 

a Genlyte Thomas Company

www.lightolier.com

Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
Copyright 2004 Lightolier

Section2/Folio G07-21

Job Information

Type:

Ordering Information

Explanation of Catalog Number. Example: LCS8G12PR232120SOGLR

Options/Accessories

Access Plate

: Top Wiring access plate is shipped with fixture as standard. When

access plates are required in advance for wiring convenience, specify separately.
Order Catalog Number: 

ACP5 CSP

.

Electrical/Wiring Options

: Consult factory.

Fusing

: Internal fast-blow fusing. Suffix: 

GLR

.

Internal slow-blow fusing. Suffix: 

GMF

.

Chicago Plenum: 

Suffix: 

CP

.

Specifications

Performance:

In an installation of 2 lamp 32W luminaires in a room cavity

ratio of 1, reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be
less than .67 with a spacing to mounting ratio of 1.4 perpendicular to the lamps.
To meet IES RP-1 for VDT areas the VCP (visual comfort probability) shall not be
less than 97 either crosswise or lengthwise and the candela value between 55°
and 90° in the 0° to 90° planes shall not exceed 839. Candelas at Nadir (0°) not
to exceed 1870.

Materials: Chassis parts

are die-formed cold rolled steel. 

Housing

is with all

edges turned-in for safe handling.

Louver:

Pre-anodized aluminum (Coilzak® or equal).

Specifications (continued)

Finish: Louver

–specular low iridescence pre-anodized reflector sheet.

Reflector:

Semi-Specular reflector sheet, 95% reflective. 

Chassis exterior

black baked polyester enamel.

Electrical: 

Thermally protected class “P” ballast C.B.M. approved, non PCB. If

K.O. is within 3" of ballast, use wire suitable for at least 90°.

Labels:

I.B.E.W./UL and ULc Listed.

Photometry

Model No. LCS8G12PR232120SO

LC

LC:

Lytecel 8"

Continuous

Blank

= Standard

N

= NYC Code

S

Body Style:

S

=Static

8

Fixture

Width

Ceiling Type:

G

= 15/16" Grid

N

= 9/16" Grid

T

= Slot Grid

12

Number of

Cells:

1 row of

12 cells

Louver Finish:

P

=Low

Iridescence
Specular

L

=Low

Iridescence
Semi-specular

R

Reflector:

R

= Semi-Specular

95%
Reflective

2

Lamp

Quantity

32

Lamp/Fixture

Length:

32

=T8

(Nominal 48")

Voltage:

120 or 277

Ballast Type:

<

20THD

<

10THD

2 Lamp Elec. T8

SO*

H

I

*

*Instant Start Standard
Other dimming options, consult factory.

DA

=DALI digital addressable dimming.

Options:

Add appropriate

suffix to catalog

no, ie: (GLR)

LER = FP - 52.1   IW - 58.0   BF - 0.87
Comparative yearly lighting energy cost per 1000 lumens = $4.61

THIS REPORT IS BASED ON PUBLISHED INDUSTRY PROCEDURES • FIELD PERFORMANCE MAY VARY FROM LABORATORY PERFORMANCE.

G03007
LCS8G12PR232120SO

coefficients of utilization — zonal cavity method  

RF

20

20

20

RC

80

50

30

RW

70

50

30

50

30

10

50

30

10

1

69

67

65

63

62

60

61

60

59

2

65

61

58

58

56

54

56

54

53

3

60

56

52

53

50

48

52

49

47

4

57

51

47

49

46

43

48

45

43

5

53

47

43

45

42

39

44

41

39

6

50

43

39

42

38

35

41

37

35

7

46

40

35

38

35

32

38

34

32

8

44

37

32

36

32

29

35

32

29

9

41

34

30

33

29

27

32

29

27

10

39

32

28

31

27

25

30

27

25

visual comfort probability 

room size

ceiling height

ceiling height

W

L

8.5

10.0

13.0

16.0

8.5

10.0

13.0

16.0

20

20

93

95

93

83

99

98

98

94

20

30

95

95

93

84

99

98

98

95

20

40

96

95

93

84

99

98

98

95

20

60

95

96

93

84

99

98

98

95

30

20

93

95

94

86

99

98

98

94

30

30

95

95

94

86

99

98

98

95

30

40

95

95

94

86

99

98

98

95

30

60

95

96

94

87

99

98

98

95

30

80

97

97

94

87

99

98

98

95

40

20

93

95

94

87

99

98

98

94

40

30

95

95

94

88

99

98

98

95

40

40

95

95

94

88

99

98

98

95

40

60

95

96

94

88

99

98

98

95

40

80

97

97

94

88

99

98

98

95

40

100

97

97

94

88

99

98

98

95

60

30

95

95

94

88

99

98

98

95

60

40

94

95

94

88

99

98

98

95

60

60

97

97

94

88

99

98

98

95

60

80

97

97

95

88

99

98

98

95

60

100

97

97

95

88

99

98

98

95

100

40

94

95

94

88

99

98

98

95

100

60

97

97

95

88

99

98

98

95

100

80

97

97

95

88

99

98

98

95

100

100

97

97

95

88

98

98

98

95

room cavity ratio

luminaries lengthwise

luminaries cr

osswise