Lightolier LUPS Series Specification Download Page 2

LUPS Series

550-1,500 VA U

NINTERRUPTIBLE

 P

OWER

 S

UPPLY

Page 2 of 2

Philips Lightolier
e: [email protected]
t: (508) 

679-8131

w: www.lightolier.com

LUPS Series  September 2, 2011

Specifications are subject to change without notice.
© Koninklijke Philips Electronics N.V., 2011. All rights reserved.

Job Information 

Type:

Ordering Information

System One-Line Diagram

Series

LUPS

 = LUPS Uninterruptible Power

Supply for Emergency Lighting Applications, 
90 Min. Backup

LUPSX

 = 10 Min. Backup

LUPSY

 = 20 Min. Backup

Voltage Configuration

A

 = 120 V Input/Output

B

 = 277 V Input/Output

550

 = 550 VA

1000

 = 1,000 VA

1500

 = 1,500 VA

VA Rating

Optional Output 
Circuit Breakers

OCB1

 = 550 VA

OCB3

 = 1,000, 1,500 VA

Factory Installed Options

FSU 

= Start-Up Service

EXT 

= Extended Warranty

1

Note
1) EXT option only available with FSU.

Output Power 

to Load

Ferroresonant 

Transformer

T1

Double 

Primary

Double 

Primary

Solid State 

Line Switch

S1

Inverter

Charger

Utility AC 

Power In

AC

AC

DC

DC

P1

P2

MODEL

LUPS550

LUPS1000

LUPS1500

CAPACITY

550 VA

1,000 VA

1,500 VA

AC INPUT 

VOLTAGES

120
277
120
277
120
277

INPUT

AMPS

1

6.5
2.8

11.5

5.0

17.2

7.4

AVAILABLE OUTPUT 

VOLTAGES/MAX LOAD AMPS

BREAKERS 

INCLUDED

1
1
3
3
3
3

Input (select one)

120 V

4.6

8.3

12.5

277V

2.0

3.6

5.4

Output (select one)

CABINET & 

ELECTRONICS

SEALED LEAD 

CALCIUM 

BATTERY

10 Min Backup

20 Min Backup

90 Min Backup

550 VA

223 lbs

(101.0 kg)

44 lbs

(19.9 kg)

54 lbs

(24.5 kg)

121 lbs

(55.0 kg)

1000 VA

223 lbs

(101.0 kg)

59 lbs

(26.8 kg)

88 lbs

(39.9 kg)

203 lbs

(92.0 kg)

1500 VA

262 lbs

(119.0 kg)

88 lbs

(39.9 kg)

108 lbs

(49.0 kg)

288 lbs

(131.0 kg)

Note
1) Maximum input current.

HEAT 

REJECTION 

(BTU/HR)

410

545

615

System Input/Output Ratings