Lightolier LOT Series Specification Download Page 2

LOT Series

5.0-10.0 

K

VA S

INGLE

 P

HASE

 UPS

Page 2 of 2

Philips Lightolier
e: lol.webmaster@philips.com
t: (508) 

679-8131

w: www.lightolier.com

LOT Series - 5.0-10.0  September 12, 2011

Specifications are subject to change without notice.
© Koninklijke Philips Electronics N.V., 2011. All rights reserved.

Job Information 

Type:

Ordering Information

On Bus w/ Optional 

Distribution

Optional Off/

Timed Off Bus w/ 

Distribution

DC 

Fuse

Battery 

Pack

Input 

Circuit 

Breaker

Inverter

Fuse

AC 

Input

SS

System Rating (kW/kVA)

Input Volt. (V):Input Curr. (A)

Output Volt:Output Current*

OCB Pole Spaces Available
     Without Trip Alarm
     With Trip Alarm
Heat Rejection (btu/hr)
Weight (lbs)  Electronics
     Empty Batt Cab
     90 Min Battery
     20 Min Battery
     10 Min Battery

5.0

120 : 54.6

120/240 : 27.3

 277 : 23.7

120/208 : 31.5

120 : 41.6

120/240 : 41.6/20.8

277 : 18

120/208 : 41.6/24
120/277 : 41.6/18

20
10

2387

840

N/A

850
350
230

System Input/Output Ratings

SS

Bypass

Output 

Hardwired 

(Standard)

P
F

C

Series

LOT

 = Single 

Phase UPS 
System for 
Emergency 
Lighting 
Applications

A

 = 120 V*

G

 = 120/240 V

J

 = 277 V

L

 = 120/208 V

Input Voltage

Qty Circuit 
Breakers

00X 

= Hardwire

01X 

= 1 OCB

02X 

= 2 OCB

03X 

= 3 OCB

04X 

= 4 OCB

.
.
20X 

= 20 OCB

01A

 = 1 OCBA

02A 

= 2 OCBA

03A 

= 3 OCBA

.
.
10A 

= 10 OCBA

(max. pole spaces 20)

LOT

Unit Size

5.0

 = 5.0 kVA

6.0

 = 6.0 kVA

7.5

 = 7.5 kVA

8.5

 = 8.5 kVA

10.0

 = 10.0 kVA

Battery Time

S

 = 90 Min

X

 = 10 Min**

Y

 = 20 Min

# Nol Circuit 
Breakers

A

 = 1

B

 = 2

C

 = 3

D

 = 4

E

 = 5 

F

 = 6

G

 = 7

H

 = 8

I

  = 9

J

  = 10

K

 = 11

L

 = 12

M

 = 13

N

 = 14

O

  = 15

P

  = 16

Q

 = 17

R

 = 18

S

 = 19

T

 = 20

Z

 = No Nol

Hardwired

System One-Line Diagram

A

 = 120 V*

G

 = 120/240 V

J

 = 277 V

L

 = 120/208 V

Y

 = 120/277 V

Output Voltage

Nol

0

 = None

1

 = Yes

T

 = Nol w/ 

TDT

Breakers On 
2nd Voltage

00

 = 2nd 

Voltage 
Hardwire 
or No 2nd 
Voltage

01
02
03
.
.
19

Nol Voltage

1

 = First

2

 = Second

3

 = Both

0

 = No Nol

Qty Nol 2nd 
Voltage

A

 = 1

B

 = 2

C

 = 3

D

 = 4

E

 = 5 

F

 = 6

G

 = 7

H

 = 8

I

  = 9

J

  = 10

K

 = 11

L

 = 12

M

 = 13

N

 = 14

O

  = 15

P

  = 16

Q

 = 17

R

 = 18

S

 = 19

Z

 = No Nol

6.0

120 : N/A

120/240 : 37.4

 277 : 32.4

120/208 : 43.1

120 : N/A

120/240 : 50/25

277 : 21.7

120/208 : 50/28.8

120/277 : 50/21.7

20
10

2864

950
350

1325

350

N/A

7.5

120 : N/A

120/240 : 42.8

 277 : 36.9

120/208 : 49.2

120 : N/A

120/240 : 62.5/31.2

277 : 27.0

120/208 : 62.5/36
120/277 : 62.5/27

20
10

3581

950
350

1500

550
350

8.5

120 : N/A

120/240 : 50.1

 277 : 43.3

120/208 : 57.7

120 : N/A

120/240 : 70.8/35.4

277 : 30.7

120/208 : 70.8/40.9
120/277 : 70.8/30.7

20
10

4058
1000

400

1500

480

N/A

10.0

120 : N/A

120/240 : 54.6

 277 : 47.3

120/208 : 63.0

120 : N/A

120/240 : 83.3/41.6

277 : 36.1

120/208 : 83.3/48

120/277 : 83.3/36.1

20
10

4774

950
350

1680
1000

900

Rectifier

Inverter 

Output 

Circuit 

Breaker

* Multi-voltage total loads not to exceed system rating.

* Only available on 5.0 kVA.
** Not available on 6.0 and 8.5 kVA.