Lightolier H9S2GLR1FT Specification Download Page 2

HP90 Recessed Fluorescent

H9S2GLR1FT

Page 2 of 2

Direct/Indirect – 2' x 2' with Acrylic Linear Prismatic Lens

Static, 1 Lamp TT5

Ordering Information

Explanation of Catalog Number. Example: H9S2GLR1FTUNVPR

Options/Accessories

Fusing:

Internal fast blow fusing: SUFFIX:

A

.

Internal slow blow fusing: SUFFIX:

C

.

Drywall Kit:

Order Catalog Number:

FK92X2

.

Electrical Wiring Options:

Consult factory.

For motion or light sensor:

See Folio OA20-10.

Specifications

Performance:

In an installation of 1 lamp 40W luminaires in a room cavity ratio of 1,

with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .96.
To reduce glare the average brightness at 65° shall not exceed 2617 candelas per square
meter. To control veiling reflections, luminaire output in the 30°-90° zone shall not be
less than 69.5%.

Materials: Chassis parts

are die-formed code gauge steel.

Lamp Shield:

Linear prismatic translucent DR acrylic lens.

Finish: Chassis exterior

– baked white acrylic enamel.

Cavity

– baked flat white

acrylic enamel. Rust preventative undercoating.

Reflector

– low iridescence specular

aluminum 95% reflectance.

Specifications

(Continued)

Electrical:

Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is

within 3" of ballast, use wire suitable for at least 90°.
UL Listed for damp locations.

Labels:

I.B.E.W./UL and ULc Listed.

This product may have a mercury containing lamp. Manage in accord with Disposal
Laws. See: www.lamprecycle.org

Options:

Add appropriate suffix

to catalog no., ie: (A)

HP90

Direct/Indirect

Recessed

S

Body Style:

S

= Static

2

Fixture

Width

G

Ceiling Type:

Fits both

Standard Grid

and

Slot Grid

L

Acrylic Lens

FT

Lamp:

(By Others)

R

Reflector:

Specular

Aluminum

1

Lamp

Quantity

1

=1 Lamp

Ballast Type:

<

10THD

1 Lamp Elec. TT5

I

B*

*

(40 Watt)

1 Lamp Elec. TT5

PR†

(40 Watt)

1 Lamp Elec. TT5

BP

(50 Watt)

1 Lamp Elec. TT5

BF

*

(55 Watt)

LOL Dimming TT5

PB

*Instant Start Standard.
Other dimming options. Consult factory.

NOTE:

For TT5 40W

UNV

, you must use PR Ballast Code.

†Program Rapid Start

0.0

45.0

90.0

FLUX

0

876

876

876

5

868

872

876

83

15

836

841

845

238

25

776

776

772

357

35

685

665

646

416

45

560

518

528

410

55

400

373

413

348

65

230

248

318

260

75

97

149

195

155

85

19

24

19

31

90

2

2

2

Model No. H9S2GLR1FTUNVPR

LER = FP - 61.2

IW - 37.55

BF - 1.0

Comparative yearly lighting energy cost per

1000 lumens = $3.92

Report Number: G2006149

Catalog Number: H9S2GLR1FTUNVPR

Lamps: F40BX/SPX30/

I

S

Luminaire: HP90 2' x 2' with linear

prismatic lens.

Ballast: C240PUNVHP-B/UNV

Report is based on 3150 Lumens per lamp.
Efficiency: 72.9%
CIE Type-Direct-Indirect

Plane:

0-Deg

90-Deg

Spacing Criteria:

1.2

1.2

Shielding Angles:

90

90

Plane:

0-Deg

90-Deg

Luminous Length:

22.800

22.800

CANDELA DISTRIBUTION

0

AVERAGE AVERAGE AVERAGE AVERAGE

IN DEG.

0-DEG.

45-DEG. 90-DEG.

45

2174.

2011.

2049.

55

1914.

1789.

1976.

65

1494.

1611.

2065.

75

1029.

1580.

2068.

85

598.

765.

598.

LUMINANCE DATA IN CANDELA/SQ. METER

COEFFICIENTS OF UTILIZATION –

ZONAL CAVITY METHOD. EFFECTIVE

FLOOR CAVITY REFLECTANCE 0.20

0

RC

80

50

30

RW 70 50 30 50 30 10 50 30 10

0

1 80 76 73 71 69 67 69 67 65

0

2 73 67 62 63 59 56 60 57 54

0

3 66 59 53 55 51 47 53 49 46

0

4 61 52 46 49 44 40 48 43 40

0

5 56 47 40 44 39 35 43 38 40

0

6 52 42 36 40 35 31 39 34 30

0

7 48 38 32 37 31 27 36 31 27

0

8 45 35 29 34 28 24 33 28 24

0

9 42 32 26 31 26 22 30 25 22

10 39 30 24 29 24 20 28 23 20

ZONE

LUMENS % LAMP

% FIXT

0

0-

0

30

678

21.5

29.5

0

0-

0

40

1093

34.7

47.6

0

0-

0

60

1851

58.8

80.6

0

0-

0

90

2296

72.9

100.0

90-180

000

0

0.0

00

0.0

0

0-180

2296

72.9

100.0

ZONAL LUMEN SUMMARY

Voltage:

120, 277 or

UNV

=120-277

H9

Standard HP90

HY

For NYC Code – I.B.E.W. Manufactured

Job Information

Type:

For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595

12/10

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710

We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group

Section 5/Folio M32-16 Rev. A

Reviews: