background image

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710

We reserve the right to change details of design, materials and finish.

www.lightolier.com © 2008 Philips Group • C0308

Job Information 

Type:

Job Name: 

Cat. No.: 

Lamp(s): 

Notes:

 

FBP Series Fluorescent Emergency Ballast

 

FBP1000-4P

Page 1 of 1 

One Lamp Operation 4-Pin Fluorescent Lamps 1,000  Lumens

Lightolier is a Philips group brand

Nickel Cadmium Battery

9.4”

(23.8 cm)

2.4”

(6.1 cm)

1.5”

(3.8 cm)

Features

1.  Lamp Operation: 

Operates the following lamp types: T4 Compact 

Fluorescent (4-pin base), 13W - 50W twin, quad and triple twin-tube without 
integral starter. See Lamp Operation and Performance table for specific lamp 

performance and operation.

2.  Illumination: 

Provides 90 minutes of emergency illumination, and produces a 

maximum of 1,000 lumens initial emergency light output. 

3.  Housing: 

Constructed of 20 gauge steel with a high temperature powder 

coat finish. Housing allows for frame mounting on most recessed luminaires. 
Housing includes 2’ lengths of flex conduit attached on each end.

4.  Electronics: 

120/277 VAC dual voltage input with surge-protected, solid-

state circuitry. Charging system is complete with AC indicator lamp and test 

switch.

5.  Battery: 

Maintenance free, sealed nickel cadmium battery has an estimated 

service life of 10 years, and an operating temperature range of 32°F (0°C) to 
131°F (55°C)

 

6.  Input Power Requirements:

 3.5 watts max.

7.  Warranty: Electronics: 

2 years; Battery: 2 years.

Code Compliance

U.L. 924 listed.

Options

EX 

= Special Input Transformer for 220 VAC/50 Hz, 240 VAC/50Hz. Contact 

factory for other input voltages and frequencies. 

Accessories

CCAPS

 = Wire bundle cover for mounting external to luminaire.

RT 

= Remote Test Switch.

Complete Fixture consists of ballast unit. Select options and accessories below.

Model # 

Max. Lumens 

Lamp Operation 

 

FBP1000-4P

 

1000 

One Lamp 4-Pin Fluorescent (without integral starter)

   

 

 

 Non-Emer.  Emer. Op. 

 

     

 

Non-Emer. 

Max. 

Max. 

Emer 

 Lamp 

 

Base 

 Lumen 

Lumen 

Lamp

 Type 

Watt.   Type 

Output 

Output 

Operation

 F18DBX/4P 

18 

G24Q-2 

1150 

500 

One or Two

 F26DBX/4P 

26 

G24Q-3 

1710 

675 

One or Two

 F18TBX/4P 

18 

GX24Q-2 

1200 

400 

One or Two

 F26TBX/4P 

26 

GX24Q-3 

1800 

600 

One or Two

 F32TBX/4P 

32 

GX24Q-3 

2200 

750 

One or Two

 F18BX 

18  2G11/4-Pin 

1250 

325 

One or Two

 F27/24BX/RS  27  2G11/4-Pin 

1800 

525 

One or Two

 F39/36BX/RS  39  2G11/4-Pin 

2850 

725 

One or Two

 F40/30BX/RS  40  2G11/4-Pin 

3150 

600 

One

 F50BX/RS 

50  2G11/4-Pin 

4000 

825 

One

 F162D/4P 

16 

GR10Q-4 

1050 

550 

One or Two

 F212D/4P 

21 

GR10Q-4 

1350 

550 

One or Two

 F282D/4P 

28 

GR10Q-4 

2050 

550 

One or Two

 F382D/4P 

38 

GR10Q-4 

2850 

675 

One or Two

F42TBXT4 

42  GX24Q-4P 

3200 

1000 

One

Notes:

 

1.  Maximum non-emergency lumen output can vary based on lamp manufacturer, ambient operating 

temperature, and ballast manufacturer.

2.  Maximum emergency lumen output is based on total output of one or two lamps, and can vary 

based on lamp manufacturer and ambient operating temperature.

3.  Maximum emergency lumen output is supported for a full 90 minutes of operation.
4.  Consult factory for compatibility, operation and performance of lamp types not listed.

Lamp Operation and Performance

Reviews: