Job Information
Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2009 Philips Group • D0609
Architectural Decorative
4F35
Page 2 of 2
Pendalux Gemini 35” Diameter Body 6-26/32/42 Triple Tube
COEFFICIENTS OF UTILIZATION ZONAL CAVITY METHOD
%EFFECTIVE FLOOR CAVITY REFLECTANCE = .20
80
70
50
30
10
50 30 10 50 30 10 50 30 10 50 30 10 50 30 10 0
1
.69 .66 .63 .60 .58 .55 .44 .43 .41 .29 .28 .27 .15 .15 .15 .08
2
.60 .55 .51 .53 .49 .45 .38 .36 .34 .25 .24 .23 .13 .13 .12 .07
3
.53 .47 .43 .46 .42 .38 .34 .31 .28 .22 .21 .19 .12 .11 .10 .06
4
.47 .41 .36 .41 .36 .32 .30 .27 .24 .20 .18 .16 .11 .10 .09 .05
5
.41 .35 .30 .36 .31 .27 .27 .23 .20 .18 .16 .14 .09 .08 .08 .04
6
.37 .31 .26 .32 .27 .23 .24 .20 .18 .16 .14 .12 .08 .07 .07 .04
7
.33 .27 .22 .29 .24 .20 .21 .18 .15 .14 .12 .10 .08 .06 .06 .03
8
.30 .24 .20 .26 .21 .17 .19 .16 .13 .13 .11 .09 .07 .06 .05 .03
9
.27 .21 .17 .23 .19 .15 .17 .14 .12 .12 .10 .08 .06 .05 .04 .02
10
.24 .19 .15 .21 .17 .13 .16 .13 .10 .11 .08 .07 .06 .05 .04 .02
DETERMINED IN ACCORDANCE WITH CURRENT IES PUBLISHED PROCEDURES
ANGLE MEAN CP LUMENS
0
826
5
824
78
10
814
15
798
226
20
184
25
776
346
30
748
35
715
422
40
675
45
626
443
50
574
55
517
409
60
456
65
396
332
70
334
75
273
230
80
216
85
164
137
90
97
CERTIFIED TEST REPORT NO. 1409FR
COMPUTED BY LSI PROGRAM **TEST-LITE**
LIGHTOLIER INDIRECT/DIRECT PENDANT FIXTURE
CAT. #4F35642WHU, 35” DIFFUSER WITH SPILL RING
6-42W T/E SYLVANIA LAMPS. LUMEN RATING = 3200 LMS.
ADVANCE BALLAST #ICF-2S42-M2-LD, 120VAC
TESTED ACCORDING TO IES PROCEDURES. TEST DISTANCE EXCEEDS FIVE
TIMES THE GREATEST LUMINOUS OPENING OF LUMINAIRE.
ZONE
LUMENS % LAMP %LUMINAIRE
0-30
649
3.38
4.08
0-40
1072
5.58
6.74
0-60
1925
10.03
12.09
0-90
2623
13.67
16.48
40-90
1551
8.08
9.75
60-90
698
3.64
4.39
90-180
13294
69.24
83.52
0-180
15917
82.91
100.00
** EFFICIENCY = 82.9% **
ANGLE MEAN CP LUMENS
90
97
95
390
536
100
1088
105
1551
1620
110
1934
115
2246
2218
120
2511
125
2646
2362
130
2729
135
2835
2195
140
2940
145
3004
1880
150
3022
155
3055
1415
160
3096
165
2936
820
170
2602
175
2537
249
180
2749
C
ANDLEPOWER SUMMARY
ZONAL LUMENS AND PERCENTAGES
DATE: MAY 4, 2001
PREPARED FOR:
LIGHTOLIER, FALL RIVER, MA
Features
1. Diffusing Reflector:
White translucent acrylic, 3/16” thick.
2. Inner Dirt Shield:
White translucent acrylic, 1/8” thick.
3. Chassis:
Steel 20 gauge, semi-gloss white powder-coat finish.
4. Suspension:
Swivel (central) stem, 5/8” steel tube. Canopy, steel, 7” Dia.
fastened internally, no exposed hardware. Permits installation on ceilings
with slope of up to 45°. Complies with California Code.
5. Multiple Stems:
3/8” Steel outer pipe stems surround center stem and go
into collector plate.
6. Lampholder:
Multi-wattage, 4-pin, will accept either GX24q-3 or
GX24q-4 lamp base.
7. Flange Trim:
Steel 20 gauge, Plated or Painted Finish.
Lamping (by others)
Compact Fluorescent:
Triple Tube, 26, 32, or 42 Watts.
General Electric
Osram/Sylvania
Philips
26W Triple Tube 4-Pin (Amalgam) Compact Fluorescent Lamp
F26TBX/*/A/4P
CF26DT/E/IN/*
PL-T26W/*/4P
32W Triple Tube 4-Pin (Amalgam) Compact Fluorescent Lamp
F32TBX/*/A/4P
CF32DT/E/IN/*
PL-T32W/*/4P
42W Triple Tube 4-Pin (Amalgam) Compact Fluorescent Lamp
F42QBK/*/A/4P
CF42DT/E/IN/*
PL-T42W/*/4P
*Manufacturers’ color temperature designation.
Electrical
Ballast
: Electronic, 2-Lamp HPF, Class P, Programmed Start.
Universal Voltage 120/277V, Multi-Wattage 26/32/42W.
6 Lamps
26 Watt
32Watt
42Watt
Voltage
120V 277V 120V 277V
120V 277V
Total Input Watts
165
165
204
204
279 279
Max. Line Current (amps)
2.22 0.96 2.80 1.20
1.20 1.60
Power Factor
>0.98 >0.98 >0.98 >0.98 >0.99 >0.99
Ballast Factor
1.02 1.02 0.96 0.96
0.95 0.95
THD<10%
Minimum Starting Temperature -5°F /-20°C.
Mounting
Mounts directly to 4” outlet box, using crossbar hanger, supplied.
Labels
cULus listed suitable for damp locations.
Application Data
Reflectancies: 80% Ceiling, 50% Walls, 20% Floor.
Light Loss Factor = .75 (.88 BF x .85)
FC (footcandles) at 30” work plane.
35 Inch Diameter
36’ x 36’ x 11’ Space
Luminaire
Spacing: 12’ x 12’
Susp. Dist. 35”
6 Lamps
26W
32W
42W
TTT
TTT
TTT
Illum. (FC)
33
44
60
Maint.
Lum.
8/1
8/1
7/1
Ratio
Watts/
1.15
1.42
1.94
Sq. Ft.