background image

 

TECHNICAL BULLETIN 

WET LOCATION RATING OF RECESSED LUMINAIRES 

 

The 2002 National Electric Code 

®

 (NEC) 

1

contains requirements addressing environmental ratings applicable to 

luminaires.  The following sections define requirements for luminaires installed in wet locations: 
 

410.4 (A) Wet and Damp Locations.

  Luminaires (fixtures) installed in wet or damp locations shall be installed so that water 

cannot enter or accumulate in wiring compartments, lampholders, or other electrical parts.  All luminaires (fixtures) installed 
in wet locations shall be marked, “Suitable for Wet Locations”.  All luminaires (fixtures) installed in damp locations shall be 
marked, “Suitable for Wet Locations” or “Suitable for Damp Locations”. 
 

Article 100, Definitions 

Location, Damp. 

Locations protected from weather and not subject to saturation with water or other liquids but subject to 

moderate degrees of moisture.  Examples of such locations include partially protected locations under canopies, marquees, 
roofed open porches, and like locations, and interior locations subject to moderate degrees of moisture, such as some 
basements, some barns, and some cold storage warehouses.

 

Location, Wet

.  Installations under ground or in concrete slabs or masonry in direct contact with earth; in locations subject 

to saturation with water or other liquids, such as vehicle washing areas; and in unprotected locations exposed to weather.

 

2

 

 
Because of the multiple variables involved, location type must be determined on a case-by-case basis.  Mounting 
height, protective cover, the likelihood of water spray and other factors must be considered.  Article 100 
(Definitions) gives parameters and examples that can assist in these determinations.  The local Authority Having 
Jurisdiction should be consulted. 
 

UL LISTING:

 To correlate with the NEC requirements regarding location, Underwriters Laboratories, Inc. (UL) 

assigns location ratings to luminaires based on their compliance with standards and testing.  Luminaires (fixtures) 
suitable for installation in wet locations as defined in the NEC must comply with the appropriate construction and 
test requirements of UL 1598 in order to be marked “Suitable for Wet Locations”. 
 

RECESSED:

 Select Lightolier recessed luminaire (fixture) finishing sections (trims) are rated “Suitable for Wet 

Locations - Covered Ceiling Mount Only”.  Lightolier rough-in sections are rated “Suitable for Damp Locations”.  
This combination allows installation where the area below the ceiling is a wet location and the area above the 
ceiling is not exposed to saturation with liquids, but may be subject to moderate degrees of moisture.  It should be 
noted that a luminaire (fixture) that complies with the UL requirements for wet locations, and is labeled as such, 
may or may not have a lens or gasket. 
 

LIGHTOLIER OPEN WET LOCATION FINISHING SECTIONS (TRIMS) 1081, 1181, 1084, 
1184 AND 2084:

  

Each of these finishing sections bear a UL Marking signifying that they are “Suitable for Wet 
Locations – For Covered Ceiling Mount Only” when installed per the supplied instructions 
and with the specified frame-in kits and lamps. 
 

The use of lamps identified as outdoor wet location rated, specific to the finishing 
section model number, is required to provide necessary shielding of the electrical 
components from liquid saturation and a lamp envelope suitable for contact with water.  Each of these 
finishing sections is also provided with a high temperature silicone gasket which, when properly installed, 
seals the lamp base, lamp holder and electrical parts and complies with UL 1598. 

 
All Lightolier recessed fixtures are Listed by UL, as evidenced by the UL Listing Mark on the products.  All Lightolier 
fixtures are intended for installation in accordance with The National Electric Code and instructions provided with 
the product.  In order to comply with applicable codes & regulations, Lightolier recommends that the local Authority 
Having Jurisdiction (building/electrical inspector) be consulted prior to installation and all necessary permits and 
inspections be obtained.

 

 
1 - Because National Electric Code requirements change from time to time, the current version accepted by the Authority Having Jurisdiction should be 
consulted prior to installation.         2 - [NFPA 70-2002] Copyright 2001 National Fire Protection Association. 
UL is a Registered Trademark of Underwriters Laboratories Inc.  The National Electrical Code & NEC are Registered Trademarks of The National Fire 
Protection Association.  All Rights Reserved. 

©

2004 by Lightolier Division of Genlyte Group LLC 

Reviews: