Welcome

LCCONTROL/4 8 0

347/480V Controller

1 (8 4 4 ) LIGHTCLOUD

1 (8 4 4 ) 54 4 -4 8 2 5

[email protected]

WE’RE HERE TO HELP:

 

 

Summary of Contents for LCCONTROL/480

Page 1: ...Welcome LCCONTROL 4 8 0 347 480V Controller 1 8 4 4 LIGHTCLOUD 1 8 4 4 54 4 4 8 2 5 support lightcloud com WE RE HERE TO HELP ...

Page 2: ...Hello The Lightcloud Controller is a remotely controlled switch and 0 10V dimming device Product Features Wireless Control Configuration Switching up to 2 A 0 10V Dimming Power Monitoring Patent Pending ...

Page 3: ...TINGS For Control of Electronic Ballast LED and Magnetic Ballast 347 480 VAC 2A Electronic Ballast LED 2A Magnetic Ballast OPERATING TEMPERATURE 40 ºC to 40 ºC OVERALL DIMENSIONS 1 58 diameter 5 90 length 1 2 NPT Mount Male 22AWG pigtails 1 6AWG pigtails WIRELESS RANGE Class 2 IP66 Rated Indoor and Outdoor Rated Wet and Damp Location Plenum Rated Line of Sight 1 0 0 0 feet Obstructions 1 0 0 feet ...

Page 4: ...t You Need Lightcloud Gateway A Lightcloud installation requires at least one Lightcloud Gateway to manage your devices 1 8 4 4 LIGHTCLOUD or 1 8 4 4 54 4 4 8 2 5 support lightcloud com WE RE HERE TO HELP ...

Page 5: ...ller GREY 0 10V DIMMING GREY 0 10V DIMMING RED RED PURPLE PURPLE WHITE WHITE BLACK BLACK BLACK BLACK 34 7 4 8 0 VAC Load or Fixture TRIGGER SENSE BROWN TRIGGER SENSE BROWN BLACK WHITE STRIPED BLACK WHITE STRIPED 3 4 7 4 8 0 V ...

Page 6: ...placed up to 1 0 0 0 feet apart If the two devices are separated by ordinary drywall construction try to keep them within 1 0 0 ft of each other Brick concrete and steel construction may require additional Lightcloud devices to go around the obstruction LightcloudGateway 100 ft Add an additional Lightcloud Device to extend network range around corners BRICK CONCRETE OR METAL WALL DRY WALL OR SIMIL...

Page 7: ...tion rating You may need to complete your low voltage wiring in another enclosure or use a partition 0 1 0 V is a common method of low voltage control of dimmable drivers and ballasts Purple 0 1 0 V positive Gray 0 1 0 V common 2a Install at a Junction Box Indoor Outdoor Controller Lightcloud RED NEUTRAL PHASE B TRIGGER SENSE BROWN PURPLE To Load To Panel To Driver Ballast LINE PHASE A GREY 0 10V ...

Page 8: ...l Alternatively break out lighting circuits and install Lightcloud devices in a separate trough Controller requires constant unswitched power When power switch is set to OFF Controller is disconnected from network OFF POWER LOAD DON T Controller always has power and is connected to the network POWER LOAD DO NEUTRAL PHASE B LINE PHASE A ...

Page 9: ...LACE RECTANGLE TO FIT CODE ON LABEL Scan Device Code Device Info Save Cancel Device ID 0013A2 004 0B62 A4 A Location Zone Name Dimmable Power Monitoring Enter Device Information Repeat for Additional Devices Devices Add Device Send Office Light ID 0013A20040B62A4A Controller Office Light ID 0013A20040B62A4B Sensor Office Light ID 0013A20040B62A4C Dimmer Office Light ID 0013A20040B62A4D Daylight Of...

Page 10: ...lluminated when device is powered Press once to highlight this device in the Lightcloud Application Press twice and hold to set dim level Press twice to toggle circuit on and off Press and hold for 1 0 seconds to remove this device from a Lightcloud network Blinks when device is indicated from the Lightcloud Application DEVICE IDENTIFICATION BUTTON Confirm Status Indicator is Solid Green see detail...

Page 11: ... dimming for a single zone REPEATER Extends the Lightcloud mesh network without controlling a load TRIGGER Detect when an attached circuit is open or closed For example you could attach the Controller in Trigger mode to an existing occupancy sensor to allow your Lightcloud system to react to the sensor OCCUPANCY LOCAL Use an attached sensor to control the Controllers load OCCUPANCY CUSTOM Use an a...

Page 12: ...d alert the Lightcloud application EMERGENCY DEFAULT If communication is lost the Controller may optionally fall back to a specific state such as turning the attached circuit on Controller requires constant unswitched power Any wires not in use must be capped off or otherwise insulated This product should only be installed by a qualified electrician and in compliance with local and national electri...

Page 13: ...ee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try and correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and ...

Page 14: ...7 Custom manufactured in China 1 8 4 4 LIGHTCLOUD 1 8 4 4 54 4 4 8 2 5 support lightcloud com Lightcloud is a commercial wireless lighting control system It s powerful and flexible yet easy to use and install Learn more at lightcloud com ...