Lifebreath AH-U-L2A-36-P16 Operation, Sizing And  Installation Manual Download Page 12

12

Air Handler Output Capacity

There are four factors that will significantly affect the heat-

ing output of the air handler.
They are:

• Hot water supply temperature (EWT)

• Hot water flow rate (GPM)

• Air Handler return air temperature

• Air Handler air flow rate (CFM)

Hot Water Supply Temperature

The hot water supply temperature is controlled by the water

heater thermostat. This is set by the installing contractor to

provide the required temperature at the hot water outlet of

the water heater.
The hot water supply temperature is typically 140°F (60°C).

If this temperature must be increased to achieve higher out-

puts from the furnace an anti-scald valve must be used to

prevent domestic hot water temperatures above 140°F

(60°C). The manufacturer of the Hot water Tank should be

consulted for temperatures higher than 140°F (60°C).
It is important that a warning label be placed near the water

heater thermostat telling the homeowner not to change the

thermostat setting. The label is included with the furnace.

Hot Water Flow Rate

The hot water entering the water coil is the source of heat to

the air handler. The effect of changing the amount of water

entering the coil is the same as changing the water tempera-

ture. As water flow is reduced, the output of the air handler

and the air temperature rise will both be lowered.

Air Handler Return Air Temperature

The return air temperature entering the air handler is

approx. 60°F (33°C) below the hot water inlet temperature.

If the return air temperature entering the air handler is

reduced, more heat transfer will occur and the output of the

air handler will increase.

Air Handler Air Flow Rate

The air entering the air handler can only be warmed by the

temperature difference between the hot water and the cool

air. As the volume (CFM (L/s)) of air is reduced, the amount

of heat which can be transferred is also reduced.

Air Handler Temperature Rise

In a fuel fired furnace, the combustion gases can be 1000°F

(538°C) above the return air temperature. These units typi-

cally have a temperature rise from 50°F (10°C) to 90°F

(32°C) and therefore delivers air at the diffuser at 120°F

(49°C) to 160°F (71°C).

With an Integrated Combo System, the hot water tempera-

ture is approx. 130°F (54°C) which is 60°F (15.5°C) above

the return air temperature. These units typically have a tem-

perature rise of 35°F (2°C) to 40°F (4°C) and therefore

would deliver air at the diffuser at approximately 105°F

(40.5°C) to 110°F (43°C).

Room Thermostat

The room thermostat controls both the water

circulation pump and the air circulation fan. It should be on

a centrally located, inside wall away from any source of

heat such as diffusers, appliances and direct sunlight.

Energy Saving Room Thermostat

A set back thermostat or “smart stat” can be used with a

combo system, but care must be taken in the timing of the

temperature changes. The timing of morning warm up

should be early enough that the desired air temperature has

been reached before the people begin to use domestic hot

water. The highest demand for space heating is during the

morning warm up and the highest demand for domestic hot

water is during morning showers. Even if the water heater

is properly sized, it may not be able to meet this combined

load. Therefore, large set backs should be avoided.

Design vs. Field Conditions

The factors discussed between design parameters and actual

field conditions can impact greatly on output capacity.

Therefore, it is important to do a thorough and complete

commissioning of the integrated combo system to ensure

the design parameters are met.

Piping

The hot water piping between the hot water tank and the Air

Handler should be new copper type, and should not be treat-

ed with chemicals, sealant or anything else, that will

interfere with the purity of the potable water. Only non-lead,

low temperature solder is permitted for sealing copper

joints.
Where possible the length of pipe should not exceed 200'

total equivalent length. Any piping running through uncon-

ditioned space must be insulated to prevent heat loss, and

possible freezing of the line.
Look inside the furnace and locate the pump. Attach the

"Hot Water In" (Supply) to the pipe running to the pump.

Attach the "Hot Water Out" (Return) to the pipe running to

the coil. Do not reverse these lines, as this will cause the

unit to malfunction.
For piping conventional water heaters, connections to and

from the Air Handler to the water tank should be made at

the point where the pipes leave the tank vertically. A "T" fit-

ting used in each vertical line, with the Air Handler piping

connected to the horizontal side of this fitting, will work

best in avoiding air locks in the circulation pump of the fur-

nace.

*Note: Remove shipping block from underneath pump and

discard.

Plumbing

NOTE

Although the water in the combo system is pressurized by
the domestic water system the pump is required to create
water flow in the heating loop. The domestic water system
applies the same pressure to the supply and return sides
of heating loop.

Summary of Contents for AH-U-L2A-36-P16

Page 1: ...LEAVE FOR HOMEOWNER NOTE Due to ongoing research and product development specifications ratings and dimensions are subject to change without notice 69 AH 091517 AIR HANDLER Models AH U S4A 24 P16 E16 AH U L4A 36 P16 E16 AH U S2A 30 P16 E16 AH U L2A 36 P16 E16 AH U L2B 48 P16 E16 ...

Page 2: ...e Breakdown 17 Specifications 18 22 Work Sheets 23 28 Wiring Diagrams 29 30 Table of Contents Air Condition coil freezing can damage the hydronic coil of the Air Handler Install a Freeze Thermostat Kit to your air conditioning coil to prevent coil freeze up Check with your air conditioner distributor to obtain a Freeze Thermostat Kit ATTENTION The Air Handler hydronic coil is not to be used for ch...

Page 3: ...keep up to its job of providing hot water for the heating system as well as other household uses Once it is correctly installed safety will never be an issue with your LIFEBREATH air handler No flames fumes or flue gases to be concerned about Your domestic hot water heater boiler now provides the heat source for your furnace This Operating and Installation Guide will help you learn about your LIFE...

Page 4: ...tems The guidelines in the manual are designed for residential forced warm air Integrated Combo Systems which utilize domestic water heaters or boilers and the LIFEBREATH furnace Heating and cooling loads shall be calculated in accordance with recognized Residential Heat Loss and Heat Gain Calculation methods Duct design shall comply with recognized Residential Air System Design methods Descriptio...

Page 5: ... systems that incorporate a pressure tank i e well systems are normally Open Systems and most municipal water systems are Closed Systems Drain Valve A drain valve is required to allow the heating loop to be drained for service or repair and to remove air from the heating loop when commissioning a system The drain valve should be near the low point of the return piping sys tem to be near the water ...

Page 6: ...ove the CAF AH This will minimize thermal siphoning in the combo system It should be noted that problems have been observed when using the side tappings on certain water heaters therefore it is strongly recommended to use the top water tappings as indicated in Figure 1 to minimize thermal siphoning and related issues Water Heater To House CAF or AH Min 12 305 mm above top of CAF AH 12 Water Heater...

Page 7: ... downstream of the heating loop connection and upstream of any domestic hot water connection The purpose of the valve is to limit the maximum tempera ture available for domestic hot water by mixing hot water from the water heater with cold water from the municipal supply The Anti Scald valve must be thermostatically controlled and approved to the ASSE standard No 1016 and 1017 for use as an anti s...

Page 8: ...use reduced bore ball valves as they are very restrictive to water flow Gate Valve The Gate Valve can be used as a shut off or drain valve When in the open position there is very little resistance to flow Gate valves tend to be less expensive than other types of valves but are susceptible to chatter noise and malfunc tion with age Globe Valve The Globe valve can be used as a shut off drain or thro...

Page 9: ...r as required as long as there is a 20 F 11 C temperature drop between the hot water supplied to the air handler and the returning water A temperature drop less than 20 F 11 C can cause the water heater thermostat not to initiate This will result in a lower hot water supply temperature or poor space heating performance with fluctuating domestic water temperatures Call for Domestic Hot Water and Sp...

Page 10: ... of water connections for the unit being installed Push fit Fittings instantly make plumbing connections thereby eliminating the need for solder Be sure to read the Push fit Fitting Installation Instructions included with the Quick Connect Fitting Kit before making any connections PART 99 CAF PKit1 2 The 1 2 assembled kit PART 99 CAF PKit3 4 The 3 4 assembled kit Quick Connect Kit PART 99 CAF PKit...

Page 11: ...pumps performance and the head pressure resistance of the complete heating loop system The piping and fittings used to connect the water heater and air handler must be sized to handle the volume of hot water required by the air handler within the pressure limitations of the circulation pump All piping fittings solders and fluxes must be acceptable for use with domestic hot water Pressure Drop PD P...

Page 12: ...r at approximately 105 F 40 5 C to 110 F 43 C Room Thermostat The room thermostat controls both the water circulation pump and the air circulation fan It should be on a centrally located inside wall away from any source of heat such as diffusers appliances and direct sunlight Energy Saving Room Thermostat A set back thermostat or smart stat can be used with a combo system but care must be taken in...

Page 13: ...he hot water heater If this is not possible or if the pip ing layout is complex the total head pressure on the pump should be calculated Ducting The duct sizing for the furnace section can be determined using HRAI Residential Air System Design Manual SMACNA or any other industry recognized manuals Note Combo units normally deliver air at approx 110 F 43 C and therefore may require larger than nor ...

Page 14: ...c style heat Off Season Circulation Timer Water is periodically circulated through the space heating loop during the summer and other periods of infrequent use The concern is that water which remains stationary in the heating loop during the summer may be less than desirable as domestic hot water when it is returned to the water heater at system startup in the fall Basic Functions C Common R 24 vo...

Page 15: ...QUALIFIÉ PEUT AJUSTÉ LES COMMUTATEURS DIP CHASSIS T44 T3 T4 T5 T6 Line Ligne T1 T2 T13 T14 T15 T16 Neutral Neutre T11 T12 2 AMPS SW1 ON 8 7 6 5 4 3 2 1 T21 T22 T23 T24 AUX 1 AUX 2 Standard 24 Volt Thermostat Connection Thermostats are not avail able through Airia Basic Functions Thermostat fan switch will control low speed fan operation Call for heating high speed Call for cooling high speed Funct...

Page 16: ... start up 1 Ensure that connecting water lines are purged and free of debris Caution solder or other debris may cause the furnace pump or check valve to malfunction 2 Blower wheel rotates freely inside its housing 3 Wiring connections are tight 4 All duct and pipe connections are sealed 5 Check that styrene block is removed from under pump 6 Front access door is on tight 7 Fan speed selection a He...

Page 17: ...still be in the water lines If so re purge the system according to the start up procedure 7 Confirm that the inlet and outlet pipe connections are not reversed 8 Ensure that there are no other restrictions in the water lines such as faulty valves or debris Pump is noisy Pumps can become noisy when air remaining in the lines interfere with their operation If this occurs re purge the system as indic...

Page 18: ...V 60Hz E16 Upgrade ECM Motor 120V 60Hz Example Model Number AH U S2A 24 P16 CFM High Speed Cooling Capacity Model Configuration AH Airhandler No HRV Refer to CAF Clean Air Furnace specifications if a built in HRV is required Available Air Handler Models AH U S2A 30 P16 E16 AH U S4A 24 P16 E16 AH U L2A 36 P16 E16 AH U L4A 36 P16 E16 AH U L2B 48 P16 E16 Refer to individual specifications pages for H...

Page 19: ...abinet All units conform to CSA and UL Standards info lifebreath com 19 Model AH U S4A 24 P16 Voltage 120 VAC 60 Hz Hp 1 3 Amps total 8 Water 1 2 13 mm Copper Connections Soldered Connection Airflow High 25 in wg 1030 CFM 5 in wg 890 CFM Net Weight 111 lbs 50 3 kg Shipping 130 lbs 59 kg Weight Date ___________________________________________ Tag _____________________Qty ___________________ Project...

Page 20: ...otal 10 6 Water 3 4 19 mm Copper Connections Soldered Connection Airflow High 25 in wg 1350 CFM 5 in wg 1180 CFM Net Weight 121 lbs 54 9 kg Shipping 140 lbs 63 6 kg Weight Note Return plenum opening available off either side of cabinet All units conform to CSA and UL Standards Date ___________________________________________ Tag _____________________Qty ___________________ Project ________________...

Page 21: ... 30 8 29 2 37 0 36 4 35 3 33 5 41 6 41 0 39 8 38 0 CFM 5 WG 46 6 45 8 44 1 42 2 51 1 50 4 48 8 46 5 S2A 30 Coil Output Chart 1000 s of BTUH 29 0 28 7 27 7 26 4 34 1 33 6 32 8 31 0 39 1 38 4 37 3 35 4 44 2 43 4 42 0 39 9 49 3 48 5 46 9 44 5 54 2 53 3 51 6 49 1 30 5 29 8 28 8 27 4 35 4 35 0 33 8 32 0 40 8 40 1 38 4 36 6 45 9 45 1 43 5 41 3 51 1 50 2 48 3 45 9 56 5 55 2 53 3 50 5 Note Return plenum o...

Page 22: ...2 8 30 2 24 7 38 5 37 8 35 3 28 9 44 2 43 3 40 4 33 1 49 8 48 9 45 6 37 3 CFM 5 WG 55 4 54 4 50 8 41 5 61 1 60 0 55 9 45 7 L2A 36 Coil Output Chart 1000 s of BTUH 35 2 34 5 32 0 25 9 41 2 40 4 37 5 30 2 47 2 46 2 42 9 34 6 53 2 52 1 48 4 39 0 59 2 58 0 53 8 43 4 65 3 63 9 59 3 47 8 36 7 36 0 33 3 26 6 43 0 42 0 38 9 31 1 49 2 48 1 44 5 35 6 55 4 54 3 50 2 40 1 61 7 60 4 55 8 44 6 68 0 66 5 61 5 49...

Page 23: ... 2 68 1 69 7 69 3 68 6 75 1 L2B 48 Coil Output Chart 1000 s of BTUH 40 7 40 4 39 9 44 1 47 6 47 2 46 7 51 6 54 5 54 2 53 5 59 2 61 5 61 1 60 3 66 7 68 5 68 0 67 2 74 3 75 5 75 0 74 0 81 9 42 8 42 5 41 9 46 7 50 0 49 7 49 0 54 6 57 3 56 9 56 1 62 5 64 6 64 2 63 3 70 5 71 9 71 5 70 5 78 5 79 3 78 7 77 7 86 6 Model AH U L2B 48 P16 Voltage 120 VAC 60 Hz Hp 3 4 Amps total 12 2 Water 1 2 13 mm Copper Co...

Page 24: ...24 ...

Page 25: ...25 ...

Page 26: ...33 T34 T35 T36 T37 T38 T39 T40 T41 T42 Contact 1 N 0 COM N C N 0 COM N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 Digital Controls Contrôles numériques N C R W Y G A C Unit Unité A C Thermostat To Vers Y To Vers C Electrical control panel service by electrician only Disconnect electrical supply prior to servicing Improper wiring may result in damage to this unit Use copper supply wires CA...

Page 27: ... N C N 0 COM N C N 0 COM Contact 2 Contact 3 Contact 4 Digital Controls Contrôles numériques N C R W Y G A C Unit Unité A C Thermostat To Y To C ORANGE N O Normally open Normalement ouvert N C Normally closed Normalement fermé COM Common Commun T Terminal P Plug Prise K Relay Relais F Fuse Fusible SW Switch Commutateur Electrica l control panel service by electricia n only Disconnec t electrica l ...

Page 28: ...or Telephone Contact Serial Number Installation Date Model TO BE COMPLETED BY CONTRACTOR AFTER INSTALLATION Register for your warranty at www lifebreath com Airia will require the Model and Serial Number to register the unit 28 69 AH 091517 ...

Reviews: