Lifasa MCE06ADV Instruction Manual Download Page 8

                                                                                                                         

Controllers MCE06ADV – MCE12ADV 

 

 

- 7 - 

3.1 

Display screen 

 

MCExxADV

    

 devices are equipped with a 3 digits x 7 segments LCD screen. The screen has also a set of 

icons,  which  provide  information  about  the  regulator  status.  The  main  indications  are:  cos

φ

  value, 

reactive  power  sign  ( 

   for lagging  or  inductive  PF  and   

  for  leading  or  capacitive  PF),  connected 

stages and measurement of different parameters (see section 3.2)  
 

Icons  

Screen and LED 

Icons Indications 

 :   Lagging or inductive 

power indication 
 

  : Leading or capacitive 

power indication 

The RUN LED (red) is ON in 
normal working conditions  

The    x10 

 Ip  LED  shows 

that the reading of current or 
max. current has to be 
multiplied by 10 

 

 

 

 

 

In normal working conditions, RUN 
LED  (red)  is  ON  and   

  cursor 

points  to  the  parameter  being 
displayed (Left column list)   

In  SET-UP mode, the RUN LED  is 
OFF,  the    cursor  is  blinking  and 
pointing  to  the  parameter  being 
configured (Right column list). 

Symbols  indicating  the  stages 
which  are  connected  (only  in  RUN 
mode) 

3.2 

Measured parameters 

When  the  instrument  is  in  normal  RUN  mode,  the  following  parameters  can  be  displayed:  cos

ϕ

,  mains 

current,  THD  of  both  mains  current  and  mains  voltage.  The  instrument  can  also  display  the  maximum 
values of mains current and voltage since the last parameters clear. The parameter being displayed can 
be selected with the navigation keys and is indicated by the   cursor. 
 

3.3 

Errors and ERROR messages 

In case that the regulator detects a possible error, the front screen shows an error code. The possible 
error codes are listed and explained in table 3-1. 
 

 Table 3-1: Possible errors and messages displayed on the screen 

ERROR 

message 

Description 

 

Load  current  below  the  threshold  current,  or  current  transformer  (CT)  not 
connected. The threshold is 0,1A at the secondary side of CT 

 

Overcompensation.  The  regulator  detects  that  some  stages  should  be 
disconnected but all the stages are already disconnected.  

 

Under-compensation.  The  regulator  detects  that  some  stages  should  be 
connected and all the stages are already connected. 

 

Overcurrent.  The  measured  current  exceeds  the  rated  current  by  a  +  20%. 
(Rated current is considered to be the CT primary rated current)  

 

Overvoltage. The measured voltage exceeds the rated voltage by a +15%. 

 

3.4 

Alarm relay 

In  case  that  the  number  of  stages  configured  in  a  MCE06ADV  or  MCE12ADV    ,  is  less  than  6  or  12 
respectively,  the  relay  number  6  or  12  is  automatically  configured  as  alarm  relay.  The  relay  remains 
connected  in  absence  of  alarm  (positive  safety)  and  disconnects  in  case  that  one  or  more  of  the  errors 
listed in section 3.2 occur. Notice that the absence of supply voltage will always be detected as an alarm 
condition.  The  alarm  relay  has  a  delay  of  10s  in  case  of  Over-compensation  and  Under-compensation, 
but the operation is instantaneous (delay < 1s) in case of Over-voltage and Over-current. 

 

Summary of Contents for MCE06ADV

Page 1: ...POWER FACTOR REGULATORS MCE06ADV MCE12ADV Instructions Manual...

Page 2: ...Controllers MCE06ADV MCE12ADV 1...

Page 3: ...8 4 INSTALLATION AND START UP 9 4 1 TECHNICAL CHARACTERISTICS 9 4 2 DEVICE INSTALLATION 10 4 2 1 Mechanical Installation 10 4 2 2 Connections 10 4 2 3 Cabling cross sections and protections 11 4 2 4...

Page 4: ...terminals have been properly connected A defective earth connection may cause a wrong operation of equipment and involves a danger of electric shock to the user or system operator Maintenance must be...

Page 5: ...ch the required PF compensation Moreover the program assigns the capacitor stages to be connected or disconnected using a FIFO criterion FIFO First IN first OUT that way the times of use of all stages...

Page 6: ...cos sometimes called Displacement Power Factor DPF in a supply network and control the connection and disconnection of power capacitors in order to regulate such parameter The difference between the t...

Page 7: ...panel shows the following items Fig 3 1 Front cover and screen NOTE The set up procedure the description of different parameters and the different control modes are described in detail in the SET UP...

Page 8: ...th the navigation keys and is indicated by the cursor 3 3 Errors and ERROR messages In case that the regulator detects a possible error the front screen shows an error code The possible error codes ar...

Page 9: ...accept configuration changes Manual connection of capacitor stages If this key is pushed for more than 1s the regulator starts connecting new steps in a sequential mode respecting the adjusted connect...

Page 10: ...n 1 5mm 2 Supply circuit protection By means of a 0 5 to 2A fuse gl type Current measurement circuit Terminals A B External Current Transformer CT Current ratio In 5 To be placed preferably in phase L...

Page 11: ...side the equipment cabinet MCExxADV devices require current sensing of the installation A current transformer CT must be installed externally to perform this function Usually the current ratio of the...

Page 12: ...V P1 P2 Fig 4 2 Connection schematic for MCE06ADV N Terminals functions A Current input S1 B Current input S2 COM Relays common 1 Relay Output 1 2 Relay Output 2 3 Relay Output 3 4 Relay Output 4 5 Re...

Page 13: ...smaller capacitor step kvar For conditions other than those given in table 5 1 the paragraph 5 13 shows a simple calculation to obtain the C K value See also foot NOTE Table 5 1 C K factor according t...

Page 14: ...ngs Taking as base the power of the smaller capacitor stage the powers of the rest of stages can be given in terms of multiples of the smaller step Then we could state the configuration configuration...

Page 15: ...tween 0 7 and 1 Table 5 3 Phase shift options in MCExxADV Screen V I phase shift at cos 1 V measured in phases CT placed in phase T1 30 L3 L2 L3 T2 270 L3 L2 L1 T3 150 L3 L2 L2 T4 210 L3 L2 L3 P1 P2 o...

Page 16: ...C K Program Delay times Nr of stages CT phase CT primary current 5 1 5 2 5 3 5 4 5 5 5 6 5 7 5 8 IMPORTANT While the device is in set up mode if there isn t any key pushing for more than 3 minutes th...

Page 17: ...equentially connect the different steps following the normal program and respecting the delay time ton set in the set up procedure long Manual disconnection of capacitor stages Keep the key pushed dur...

Page 18: ...gh the regulation may be wrong the device tries to regulate the PF normally Overvoltage The measured voltage is 15 above rated voltage Possible causes Connection to a wrong supply voltage Alarm relay...

Reviews: