![Liebert TCDV165 Product Information Manual Download Page 6](http://html1.mh-extra.com/html/liebert/tcdv165/tcdv165_product-information-manual_1907339006.webp)
Introduction
2
Figure 2
Major electrical control components
Table 1
Electrical data—50 and 60 Hz
Model #
165, 205
251, 308
415, 510
Number of Fans
2
3
4
Input Voltage
Ph
Hz
Motor Hp
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
208/230
3
60
0.75
7.2
8.1
15
10.7
11.6
15
14.2
15.1
20
460
3.5
4.0
15
5.2
5.7
15
6.9
7.4
15
200/230
50
7.2
*
*
10.7
*
*
14.2
*
*
380/415
3.5
*
*
5.2
*
*
6.9
*
*
FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device Rating
* = Follow local electrical code to determine WSA and OPD
Table 2
VFD condensers for indoor units, 50 and 60Hz
Indoor Unit
R-22
R-407C
Outdoor Design Ambient Temperature
95°F
(35°C) 100°F
(38°C) 105°F
(41°C)
95°F (35°C)
100°F (38°C) 105°F
(41°C)
DH/VH75A
N/A
N/A
TCDV165
N/A
N/A
N/A
DH/VH114A
TCDV165
TCDV165
TCDV205
N/A
N/A
N/A
DH/VH125A
TCDV165
TCDV165
TCDV205
N/A
N/A
N/A
DH/VH199A
TCDV205
TCDV308
TCDV308
N/A
N/A
N/A
DH/VH245A
TCDV308
TCDV308
TCDV415
N/A
N/A
N/A
DH/VH290A
TCDV308
TCDV415
TCDV415
N/A
N/A
N/A
DH/VH380A
TCDV415
TCDV510
N/A
N/A
N/A
N/A
DS/VS028A
TCDV165
TCDV165
TCDV205
TCDV205
TCDV205
TCDV251
DS/VS035A
TCDV165
TCDV205
TCDV205
TCDV205
TCDV205
TCDV251
DS/VS042A
TCDV205
TCDV205
TCDV308
TCDV205
TCDV251
TCDV308
DS/VS053A
TCDV205
TCDV308
TCDV308
TCDV251
TCDV308
TCDV415
DS/VS070A
TCDV308
TCDV415
TCDV415
TCDV308
TCDV415
TCDV415
DS/VS077A
TCDV308
TCDV415
TCDV510
TCDV308
TCDV415
TCDV510
DS/VS105A
TCDV415
TCDV510
N/A
TCDV415
N/A
N/A
Variable
Frequency
Drive control
Liebert’s
Transient
Voltage
Surge
Suppression
Locking
Disconnect