Troubleshooting

24

9.0

T

ROUBLESHOOTING

The information below indicates various symptoms a user may encounter if the Liebert PSI XR expe-

riences a problem. See 

Table 9

 for suggested solutions.

1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for 

low battery, overload warning and fault.

2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator, 

as described below:

If the UPS fails to operate properly, turn Off the unit and repeat the steps in 

3.0 - Installation

. If the 

problem persists, refer to 

Table 9

.

Table 9

Troubleshooting—problems, causes and solutions

Problem

Cause

Solution

UPS will not start

Short circuit

Check the circuit breaker on the 

rear of the UPS.

If it is tripped, reset it and restart the 

UPS. For help, contact your local 

dealer, Emerson representative or 

Liebert Applications.

Battery is disconnected or 

completely discharged

Check for proper connection of 

battery or batteries.

UPS starts on battery, but will not 

switch to AC (dark start)

UPS not plugged in

Plug in the power cord securely.

Circuit breaker tripped

Reset the circuit breaker and restart 

the UPS.

AC overvoltage

Wait until voltage drops to an 

appropriate level or have the utility 

power checked by a properly 

trained and qualified electrician.

UPS shuts down

Short circuit or UPS output is 

abnormal; LED 10 and LED 11 

illuminate and sound audible 

alarm

Remove the load and turn on the 

UPS again. For help, contact your 

local dealer, Emerson 

representative or Liebert 

Applications.

Overload; LED 5 and LED 11 

illuminate and sound audible 

alarm

Check load level display and 

remove nonessential loads. 

Recalculate the load and reduce 

equipment connected to UPS - the 

total wattage must not exceed the 

capacity of the UPS.

LED 3 and LED 11 illuminate and 

sound audible alarm

Recharge the battery for 8 hours, 

then turn ON the UPS.

Liebert MultiLink shutdown 

software

Consult the Liebert MultiLink 

software user manual or contact 

your LAN administrator.

Site Wiring Fault LED (LED 4) flashing

Site Wiring Fault, UPS detected a 

line-to-neutral reversal or a loss of 

proper grounding.

Have the utility checked by a 

properly trained and qualified 

electrician.

Battery weak LED (LED 3) flashing

Batteries weak

Recharge batteries.

Batteries need to be replaced

Replace batteries.

NOTE

The 1920VA UPS will sound an Overload alarm under certain Low Line conditions when it is 

fully loaded and it exceeds the input current rating. Unless the load is reduced, the condition 

will trip the branch circuit breaker.

Summary of Contents for PS1000RT3-120XR

Page 1: ...AC Power For Business Critical Continuity Liebert PSI XR User Manual 1000 1500 1920 3000VA 60Hz 120VAC...

Page 2: ......

Page 3: ...15 4 1 1 On Alarm Silence Manual Self Diagnostic Test 15 4 1 2 Off Button 15 4 2 Status Indicators 15 4 2 1 Status Change Button 15 4 2 2 Load Level Indicator 15 4 2 3 Battery Level Indicator 16 4 2...

Page 4: ...rge protection 11 Figure 12 Connect computer interface port 11 Figure 13 EPO connection for normally open operation 12 Figure 14 Install the external battery cabinet in tower installation 12 Figure 15...

Page 5: ...r fire To ensure safety observe the following rules Turn Off and unplug the UPS before cleaning it Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners Do not install or operate the UP...

Page 6: ...re of the following measures Reorient or relocate the receiving antenna Increase the separation between the UPS and the receiver Connect the UPS to an outlet on a circuit different from the one the re...

Page 7: ...s caution followed by important instructions Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Alarm Silen...

Page 8: ...n including voltages currents and alarm status to the host system when used in conjunction with Liebert MultiLink shutdown software Figure 1 Front view of UPS rack mount Figure 2 1000 and 1500VA rear...

Page 9: ...reaker Receptacles 1 and 2 Receptacles 1 and 2 NEMA 5 20R T Slot Receptacles 3 and 4 NEMA 5 15R Liebert IntelliSlot Port DC 48V OUTPUT EPO INPUT VOLTAGE 110V VOLTAGE 120V VOLTAGE 127V 2 1 FUNCTION NEM...

Page 10: ...9 Serial Cable USB Cable Tower Stand Rack Mount Handles Battery UPS Tab Mounting Hardware Fixed Mounting Rails EPO Connector Figure 5 Accessories Liebert Shutdown Software Program Liebert MultiLink Sh...

Page 11: ...low around the unit away from water flammable liquids gases corrosives and conductive contaminants see Figure 6 Maintain a minimum clearance of 12 inches 305mm in the front and rear of the UPS Maintai...

Page 12: ...Installation 8 3 2 Tower UPS Installation See Figure 7 when using the Liebert PSI XR in a tower configuration Figure 7 Tower configuration attach Tower Stand Step 1 Step 2...

Page 13: ...s on each side The rack mount handles WILL NOT support the weight of the UPS They are used to move the UPS into and out of the rack WARNING Placing heavy equipment near the top of a rack may increase...

Page 14: ...ly then press it into the UPS until it is seated Figure 9 Adjusting the UPS display 3 5 Connect Input Power and Load Connect input power to the UPS then plug the equipment into the outlets on the rear...

Page 15: ...al contact closure USB SNMP Connect the appropriate factory supplied cable to the interface port on the rear of the UPS and to the computer interface port See the Liebert MultiLink shutdown software u...

Page 16: ...ttery cabinet cable to the rear of the external battery cabinet then to the rear of the UPS see Figure 15 Figure 14 Install the external battery cabinet in tower installation NOTICE External battery c...

Page 17: ...Installation 13 Figure 15 Connect battery cabinets to UPS See Table 8 for approximate battery run times DC 24V OUTPUT INPUT EPO VOLTAGE 110V VOLTAGE 120V VOLTAGE 127V 2 1 FUNCTION...

Page 18: ...n in AVR Buck Mode 3 LED 3 Battery Condition Battery Fault Weak 4 LED 4 Grounding Site Wiring Fault UPS Grounding Site Wiring Fault 5 LED 5 Overload UPS Overload 1 to 5 Load Battery Level Indicate Loa...

Page 19: ...ct your local dealer Emerson representative or Liebert Applications If LED indicates UPS Fault Remove the load retest the self diagnostic test if LED indicated UPS Fault Contact your local dealer Emer...

Page 20: ...indi cate the mode Weak Battery When the UPS battery voltage is low the LED display will indicate the relative load level on the output of the UPS and LED 3 will flash as a warning Site Wiring Fault...

Page 21: ...en when the UPS is in Boost Mode LED 2 flashes green and LED 9 illuminates steady green when the UPS is in Buck Mode see 9 0 Trouble shooting for details 5 3 Battery Mode The UPS switches to Battery M...

Page 22: ...he pins are shorted When the short is removed the UPS output can be enabled by pressing the ON Alarm Silence Manual Self Diagnostic button 6 2 2 Battery Mode Shutdown Via Pins 4 5 While the UPS is ope...

Page 23: ...UPS Inverter Transfer Voltage Configurations A two pin DIP switch on the rear of the PSI XR permits setting the UPS to operate at nominal volt ages of 110V 120V or 127V This feature will change the hi...

Page 24: ...ries 1 Remove the two screws on the left side of the front bezel 2 Pull the front bezel off the UPS 3 Remove the screw on the battery connectors holder 4 Remove the two screws on the battery bracket 5...

Page 25: ...EMA 5 20R T Slot accepts15A Plug 1 NEMA L5 30R Voltage Normal Mode 110 120 127 VAC configurable Voltage Battery Mode 110 120 127 VAC 5 before low battery warning Transfer Time 4 6 ms typical Battery W...

Page 26: ...pping 22 x 26 6 x 9 560 x 675 x 228 Weight lb kg Unit 64 29 Shipping 73 33 Batteries Type Valve regulated nonspillable lead acid Quantity x Voltage x Ah 8 x 12 x 7 2 8 x 12 x 7 2 Manufacturer CSB YUAS...

Page 27: ...Internal Battery 3 External Battery Cabinets 10 614 492 322 267 25 324 241 170 139 50 181 131 95 73 75 126 84 62 50 100 96 64 48 31 Internal Battery 4 External Battery Cabinets 10 789 627 483 329 25...

Page 28: ...e Wait until voltage drops to an appropriate level or have the utility power checked by a properly trained and qualified electrician UPS shuts down Short circuit or UPS output is abnormal LED 10 and L...

Page 29: ...Troubleshooting 25 Notes...

Page 30: ...Troubleshooting 26...

Page 31: ......

Page 32: ...oration All names referred to are trademarks or registered trademarks of their respective owners Technical Support Service Web Site www liebert com Monitoring 800 222 5877 Liebert monitoring emerson c...

Reviews: