10
SPECIFICATIONS
Model # / Stock #
PS250-50/PS250-50S
PS400-50 / PS400-50S
PS600-50 / PS600-50S
Model Rating
250 VA / 150 W
400 VA / 240 W
600 VA / 360 W
Dimensions: mm
Unit (W x D x H)
90 x 262 x 175
109 x 262 x 186
124 x 262 x 216
Shipping (W x D x H)
181 x 365 x 303
212 x 482 x 292
237 x 482 x 334
Weight: Kg
Unit
4
5.7
9
Shipping
4.6
7
10.5
AC Parameters
Receptacles
(2) CEE-22
(4) CEE-22
(4) CEE-22
Input Voltage Range
180-300 VAC, Single Phase, 2 Wire Plus Earth
Low Voltage Transfer Point
190 VAC, User Selectable to 180 or 200 VAC
High Voltage Transfer Point
270 VAC
270 VAC, User Selectable to 280 VAC
Input Frequency Range
47 – 53 Hz, 57 – 63 Hz
Spike Protection
80 Joules
Output Voltage (on battery)
230 VAC, ± 5%
Output waveform (on battery)
Stepped Sine Wave
Max. Output Current at 230 V
1.1 A
1.7A
2.6A
Output Frequency
50 or 60 Hz, ± 5%
Max. Overload Capacity
115% of Power Rating
Battery
Type
Valve-Regulated Lead Acid
Qty x Voltage x Rating
1 x 12 V x 4.5 AH
1 x 12 V x 7 AH
2 x 12 V x 7 AH
Back-up Time
6 minutes at full load
Time from Low Battery Alarm
to Shutdown
Approximately 2 Minutes, depending on load
Recharge Time
8 – 10 Hours to 90% Capacity
Battery Life
3 – 5 Years Typical
Transfer Time to/from Inverter
2 – 6 msec. Typical
Agency Approvals
Safety
EN 50091-1
RFI
Meets EN 55022 Class B, IEC 801-2, 3, 4
Surge Protection
Meets IEC 801-5 (Draft)
MTBF (Bellcore Method)
100,000 Hours (Excluding Battery)
Environmental Standards
Operating Temperatures
+10° C to +40° C
Storage Temperatures
-20° C to +40° C (High Temperatures Reduce Battery Life)
Cooling
Convection
Audible Noise
Less than 40 dB @ 1 meter
Operating Elevation
Up to 3,000 m
Storage Elevation
Up to 10,000 m