Site Preparation and Installation
27
Liebert
®
Mini-Mate2
™
5.5.4 Condensate Pump Kit Installation—All Units
1. Refer to detail instructions and drawings supplied with the pump.
2. Disconnect all power to the unit.
3. Remove access panels.
4. Use mounting brackets if pump is not attached to ductwork. Pump inlet must be at least 1/2 in.
(12.7mm) below evaporator drain. Mount the pump to unit exterior as shown in
Figure 15
.
5. Connect 3/4 in. flexible rubber tubing with hose clamp (both supplied with pump kit) to 3/4 in.
hose barb fitting on pump.
6. Connect evaporator drain to 3/4 in. NPT-Female hose assembly on pump inlet using 3/4 in. hard
pipe with no trap in the line. Provide at least 1 in. (25.4mm) clearance between the access panel
and the drain line. Support piping as required.
7. Connect a drain line to the pump discharge 3/8 in. O.D. Cu (compression fitting provided).
8. Connect electric leads L1 and L2 to the line voltage terminal block in the cooling unit. Connect the
ground lead to the lug near the terminal block.
9. Connect wires from the Auxiliary Pump contacts to terminals TB1-8 and TB1-9 to shut down unit
at the occurrence of a high water condition in the pump.
10. Reinstall the access panels.
11. Reconnect power to the unit.
12. Run the unit to make sure the pump works properly. Operate the pump and check the drain line
and discharge line for leaks. Correct as needed.
5.5.5 Electrical Connections
Each unit is shipped from the factory with internal wiring completed. Refer to electrical schematic
when making connections. Electrical connections to be made at the installation site are:
• Power supply to each ceiling unit.
• Control wiring between the evaporator unit and the condensing unit, if applicable.
• Control wiring between the control panel (wall box) and the evaporator unit control board.
Entrance locations for these connections are noted on drawing in each installation section.
!
WARNING
Risk of electric shock. Can cause injury or death.
Open all local and remote electric power disconnect switches before making electrical wiring
connections.
NOTE
Remove any shipping bands from float switch in evaporator pan
NOTE
3/4" flexible rubber tubing assembly (supplied with pump kit) must be installed on pump end
of rigid piping (field-provided and supported as required).
!
WARNING
Arc flash and electric shock hazard. Open all local and remote electric power disconnect
switches and wear protective equipment per NFPA 70E before working within the electric
control enclosure. Failure to comply can cause injury or death.
Unit contains hazardous voltage/electric power.
Line side of factory disconnect remains energized when factory disconnect is Off.