Controls
6 -- 2
Liebert HPC---S 006---022---PD---273571---01.03.2012
iCOM Technical Data
Technical Data
iCOM Medium
E2prom
4 Mbit + 512 kbit
Flash memory
32 Mbit
RAM memory
128 Mbit
Microcontroller
Coldfire 32 Mbit
Analogue Input
3 x 0---10V, 0---5V, 4..20mA (selectable) + 2 PTC/NTC + 3 NTC
Digital Input
9 x opto---coupled
Analogue Output
2 x 0---10V
Digital Output
7 triacs output and 2 relay output
Time and date
Buffered by an LI---battery
Hirobus Lan connectors
2 RJ45 sockets (for unit in LAN, remote display)
Ethernet network connectors
1 RJ45 socket
CAN bus connectors
1 RJ12 sockets
Hironet connectors
1 RJ10 socket for RS485 (direct connection to proprietary supervision)
RS232 service port
---
CDL Graphic Display
(special option fitted on Electrical Panel chiller board or optional for indoor
remote IP40 Box installation)
The CDL graphic display featuring a 24h / 8 days graphic record of con-
trolled parameters as well as the last 200 events occurred.
A back---up battery keeps the data stored in the memory (graphic data re-
cord, alarms).
D
Medium graphic display (320 x 240 pixel).
D
System Window: system operation status at a glance.
D
Self---explanatory Icons: they are used for the Menu---Layout of the
CDL iCOM.
D
Online Help: every single parameter has its own multi---page explana-
tion.
D
Status Report of the latest 200 event/messages of the unit/system.
D
Four different Graphic Data Records.
D
Timer and Date mode (electronic timer included in the software).
D
Semi or full manual mode software management including all safety devices.
D
4---Level passwords system to protect all the settings.
D
Ergonomic design for use also as portable device (start---up and ”flying connections” by service per-
sonnel).
D
Multi---language menu with on---the---fly language selection.
CDL Technical Data
D
Microcontroller:
Coldfire 32 bit;
. . . . . . . . . . . . . . . . .
D
Ethernet network connectors:
2 RJ45 sockets (for unit in LAN, remote display);
. . . . .
D
CAN bus connectors:
2 RJ12 sockets;
. . . . . . . . . . . .
D
Power supply:
via CAN bus or external 12 Vdc supply.
. . . . . . . . . . . . . . . . . .
Liebert HPC---S 006---022 Connectivity
iCOM and CDL allow Connectivity with superior levels of control and supervision systems:
Hirovisor IP software
This software allows distance monitoring and telemaintenance, and also the storing in the personal com-
puter of the graphics of water temperature trends and status reports for archiving purposes. Delivery of
SMS and e---mail is supported.
BMSs connections
The IS cards and other gateway represent the communication managers portfolio which allow the integ-
ration of the
Liebert HPC---S 006---022
units into the most diffused Building Management Systems. The
most diffused are: SNMP, HTTP, MODBUS and LONWORK.
Summary of Contents for HPC-S 006
Page 50: ......