Hinet UPS User Manual
(12/01)
Page 31
7.11
Remote Alarm Monitor
The RAM is realised to provide the user with a visual and audible indication of the UPS status.
It will be connected to the communications relays card of the UPS via user supplied cabling (maximum length 100m).
The RAM shall be supplied from a single phase system using an external power supply
The RAM is provided with LEDs and a horn to reflect the status of the UPS communications relays as detailed below. A
horn cancel button allows the user to mute the audible alarm for the current status. An additional LED indicates that the
RAM is operating correctly.
LED Name
LED
Color
LED
Status
HORN
Status
CONDITIONS
UPS On
Green
On
Off
Inverter operating.
Off
On
Inverter not operating
On Bypass
Amber
On
Off
Load is being supplied through the bypass
Off
Off
Load is not being supplied through the
bypass
On Battery
Amber
On
On
Load is being supplied from battery power
Off
Off
Load is not being supplied from battery
power
Low Battery
Red
On
On
Shutdown imminent due to depleted battery
Off
Off
Shutdown is not imminent due to depleted
battery
Monitor
Power
Green
On
Off
Power to the RAM is present and within
specification
Off
Off
Power to the RAM is absent or outside
specification
The Hinet terminal block need to be connected to the RAM in the following way
PIN
ASSIGNMENT DESCRIPTION
2
NC Low Battery
3
COM Low Battery
4
NO UPS Run
6
COM UPS Run
7
NO Bypass ON
9
COM Bypass ON
11
NC Main Status
12
COM Main Status
Where
NC
?
Normal Close Contact
NO
?
Normal Open Contact
COM
?
Common
Summary of Contents for Hinet 10kVA
Page 2: ......
Page 7: ...USER MANUAL Hinet UPS System 12 01 Page V...
Page 10: ......
Page 14: ...Hinet UPS User Manual Page 4 12 01...
Page 22: ...Hinet UPS User Manual Page 12 12 01...
Page 30: ...Hinet UPS User Manual Page 20 12 01...
Page 37: ...Hinet UPS User Manual Chapter 6 Optional Equipment 01 Page 27...