Summary of Contents for Hinet 10kVA

Page 1: ...Manual Reference number 6390001 H 2 12 01 RevENPAu07 2002 H HI IN NE ET T U UP PS S S SY YS ST TE EM M 1 10 0 3 30 0 k kV VA A 3 3x x1 1 U Us se er r M Ma an nu ua al l...

Page 2: ......

Page 3: ...rter 1 Frequency Converter 3 Harmonic Filter 0 No 3 Harmonic Filter 1 3 Harmonic Filter THDi Reduction Filter 0 No THDi Reduction Filter 1 THDi filter for 10kVA Unit 2 THDi filter for 15 20kVA Unit 3...

Page 4: ...HNBATTCAB 38Ah 5 Years Batteries for External Battery Cabinet 32 Bloks x 12V HN38AH5Y 65Ah 5 Years Batteries for External Battery Cabinet 32 Bloks x 12V HN65AH5Y Hinet Additional Communications Card K...

Page 5: ...must be protected from rain or excessive moisture and installed in a clean environment free from flammable liquids gasses or corrosive substances Do not put drinks plants or any other containers holdi...

Page 6: ...service batteries e Eye protection must be worn to prevent injury from accidental electrical arcs f Remove rings watches necklace s bracelets and all metal objects g Only use tools with insulated hand...

Page 7: ...USER MANUAL Hinet UPS System 12 01 Page V...

Page 8: ...ting options on the standard Relay Card 9 3 2 2 Remote EPO Emergency Power Off 10 3 2 3 Emergency Power Off E P O push button connection 10 3 2 4 Connection to Personal Computer 10 3 2 5 UPS Monitorin...

Page 9: ...NPUT FILTER FOR CURRENT THD REDUCTION INTERNAL OPTION 28 7 6 INPUT 3 HARMONICS FILTER INTERNAL OPTION 28 7 7 INTERNAL EXTENDED BATTERY KIT 28 7 8 BATTERY CONNECTING KIT 28 7 9 EXTENDED BATTERY CABINET...

Page 10: ......

Page 11: ...steel frame with removable panels The door can be open to give easy access to the input bypass output reserve line circuit breakers and battery C B fused switch while protecting them from accidental...

Page 12: ...d UPS fault In the event of an inverter failure the automatic by pass will automatically transfer the load onto the mains with no interruption In such an event request qualified technical assistance T...

Page 13: ...the Common Bypass configuration In the Split Bypass configuration the static bypass line is connected by a separate power switch to a dedicated bypass power source that also feeds the maintenance byp...

Page 14: ...Hinet UPS User Manual Page 4 12 01...

Page 15: ...emove the extruded elements utilised as packing protection Use the extractor to remove all lateral sides of the crate Slide the forks of the lift truck under the UPS and after having lifted it a few c...

Page 16: ...nce around the front of the equipment should be sufficient to enable free passage of personnel with the door fully opened 2 1 7 Raised floor installation If the equipment is to be located on a raised...

Page 17: ...arthed in accordance with local regulations WARNING FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN ELECTRIC SHOCK HAZARD TO PERSONNEL OR THE RISK OF FIRE SHOULD AN EARTH FAULT OCCUR BEFO...

Page 18: ...ut Mains phase V1 4 Input Mains phase W1 5 Input Mains Neutral N1 6 Input Reserve Bypass phase U3 7 Input Reserve Bypass Neutral N3 8 Battery Positive ext Battery input 9 Battery Negative ext Battery...

Page 19: ...side of the rear panel This card is typically supplied and is factory pre set to operate with the PC When the operation is through the Remote Alarm Panel the factory will deliver the card already pre...

Page 20: ...nnel must remove protection panel held in place with screws 3 2 3 Emergency Power Off E P O push button connection Refer to figure 3 2 to make a push button connection to the standard Relay Card 1 Get...

Page 21: ...ntellislot communications port for the optional internal Ethernet SNMP card The Intellislot SNMP Card provides SNMP based management to your UPS The card gives you the power to monitor and control you...

Page 22: ...Hinet UPS User Manual Page 12 12 01...

Page 23: ...sists in a LCD display that indicates the operational and alarm status of the UPS and the EPO push button that is located at the left side The LCD Display Panel displays textual messages and operating...

Page 24: ...menu the User may have access to different menu pressing the MENU Button second level Once in this level the first row will show menu choice and the NEXT and BACK push Button enable the User to move f...

Page 25: ...BACK CLOCK NEXT UPS CONFIGURATION NEXT BACK BATTERY TEST NEXT BACK SWITCH LOAD NEXT INVERTER ON OFF NEXT BACK DISPLAY EVENTS NEXT DELETE EVENTS ENTER NEXT BACK ITALIAN NEXT BACK ENGLISH NEXT FRENCH NE...

Page 26: ...he inverter LOAD ON BYPASS The load is supplied from the bypass line This can be a temporary condition lasting for 20 sec when a fast overload occurs UPS in Alarm In case of a failure in the UPS the d...

Page 27: ...estart the UPS Fully switch off the Breakers and the Battery Fuse wait till the LCD is complete switch off then restart the UPS BATTERY NOT CONNECTED Battery Switch Open Battery Test Failed BATTERY CH...

Page 28: ...ENTER CLEAR ENTER CLEAR DATE TIME LAST EVENT EVENT CANCELLED BACK CLEAR DATE TIME PREVIOUS EVENT N 1 BACK CLEAR DATE TIME PREVIOUS EVENT N 2 MENU MENU ENTER EVENT CANCELLED ENTER EVENT CANCELLED ENTER...

Page 29: ...scroll consecutive numbers use BACK and NEXT buttons to move on the left use MENU button Then type the whole Date and press ENTER to confirm If something is wrong in the Date or Time the message ERRO...

Page 30: ...Hinet UPS User Manual Page 20 12 01...

Page 31: ...net The location of the UPS power switches is shown in Figure 5 1 The UPS power switches are INPUT MAINS SWITCH connects the UPS to the mains input supply RESERVE SWITCH Bypass connects the UPS to the...

Page 32: ...T MAINS switch 5 Switch ON the BATTERY switch 5 2 2 Inverter Turn on and LCD panel LEDs activation When switching ON the UPS will set to the automatic By pass condition yellow LED BYPASS ON thus produ...

Page 33: ...the load from the UPS inverter output to the maintenance bypass system This may be required during UPS maintenance procedures The manual bypass allows to exclude the UPS while still keeping the load...

Page 34: ...ff MAINTENANCE BYPASS switch manual 6 switch on the inverter pressing ENTER in the INVERTER ON OFF display The load is once again powered from Hinet Place the mechanical lock and eventually the pad lo...

Page 35: ...Voltage Adjustment Range Nominal 5 Output Voltage Stability Static Balanced Load Dynamic 50 Load Step Dynamic 100 Load Step 1 3 5 Output Voltage Transient Recovery Time 30ms to 3 RMS Output Voltage Di...

Page 36: ...luding Battery Charging 50 Linear Load 100 Linear Load 88 91 88 91 89 92 90 92 Full Load Inverter Efficiency 94 94 94 94 Operating Temperature Range 0 40 C 20 C for optimal battery life time Storage T...

Page 37: ...Hinet UPS User Manual Chapter 6 Optional Equipment 01 Page 27...

Page 38: ...installation unit configuration 7 4 Isolation Transformer Internal Option The isolation transformer in a star star configuration can be connected either in the input or output side This Item is place...

Page 39: ...ttery harness Frontal cover metallic plates to protect internal connections fixed by screw 8 mm size The total weight of the cabinet full of battery 65Ah is 900 kg Battery Assembling Instruction 1 Pla...

Page 40: ...V Dimensions mm L 197 W 165 H 170 over Terminals Weight 13 9 kg Terminal D 5 5mm or M5 To Terminal blocks UPS Position Length Quantity Type 1 150 mm 16 Connection 1 2 800mm 12 Connection 2 3 1400mm 3...

Page 41: ...S UPS On Green On Off Inverter operating Off On Inverter not operating On Bypass Amber On Off Load is being supplied through the bypass Off Off Load is not being supplied through the bypass On Battery...

Page 42: ...ngement as shown below PIN ASSIGNMENT DESCRIPTION 1 NC Low Battery 2 NO UPS Run 3 NO Bypass ON 4 NC Main Status 5 COM 7 12 Frequency Converter Allow to have 50Hz Input and 60Hz Output or vice versa No...

Page 43: ...ed modification alteration or repair use beyond rated capacity or improper installation maintenance application or use including without limitation use in a manner contrary to the accompanying instruc...