Guide Specifications
2.0 PRODUCT
2.1
FABRICATION
All materials and components making up the UPS shall be new, of current manufacture and shall not have been in
prior service except as required during factory testing. All relays shall be provided with dust covers.
2.1.1 Wiring
Wiring practices, materials and coding shall be in accordance with the requirements the standards listed in
Section 1.2 and other applicable codes and standards. All wiring shall be copper.
2.1.2 Cabinet
The UPS unit shall be composed of: input PFC converter, battery charger, dual-inverter, input filter and internal
bypass circuit; and batteries consisting of the appropriate number of sealed battery cells; and shall be housed in a
rack-tower NEMA type 1 enclosure and shall meet the requirements of IP20. The UPS cabinet shall be cleaned,
primed and painted RAL 7021 Black. The internal battery unit shall be shipped separately and shall be installed
during the UPS installation process.
2.1.3 Matching Battery Cabinets
The optional Rack-Tower battery cabinet shall contain valve-regulated, non-spillable, lead acid cells, housed in a
separate cabinet that matches the UPS cabinet styling. The cabinet shall be cleaned, primed and painted Black
RAL 7021. The external battery system shall be sized to provide an additional 9-11 minutes of reserve power at
rated load. The matching battery cabinet shall include an 18" (0.45m) detachable, molded interconnect cable,
circuit breaker overcurrent protection and provisions for daisy-chain connection of additional battery cabinets.
The model numbers, dimensions and weight information of the UPS cabinet and optional external battery cabinet
shall be as follows:
Model
Rack Dimensions
W x D x H, in. (mm)
Tower Dimensions
W x D x H, in. (mm)
Weight
lb. (kg)
GXT3-5000RT208
16.9 x 26.1 x 6.8
(430 x 662 x 173)
6.8 x 26.1 x 16.9
(173 x 662 x 430)
132 (59.9)*
GXT3-6000RT208
16.9 x 26.1 x 6.8
(430 x 662 x 173)
6.8 x 26.1 x 16.9
(173 x 662 x 430)
132 (59.9)*
GXT3-144VBATT
(Optional External Battery)
16.9 x 26.1 x 3.3
(430 x 662 x 85)
3.3 x 26.1 x 16.9
(85 x 662 x 430)
99.9 (45.3)*
* Specified weights include the standard internal battery kit (1), Part Number GXT3-144BATKIT.
2.1.4 Cooling
The UPS shall be forced air cooled by internally mounted, continuous fans. Fan power shall be provided from the
internal DC supply. Air intake shall be through the front of the unit, and air exhaust shall be out the rear of the
unit.