30 Chapter 3 Electrical Installation
DM Series 16kW Air Conditioner User Manual
Analog main menu interface
Press the ENT key to enter the analog submenu interface when the current main interface shows
‘F--’ (the symbol of
analog main menu). The switching operation processes and orders of the analog submenu are shown in the following
figure.
ENT key
DOWN key
ESC key
UP key
F
F01
F02
F03
F04
F05
F06
16.1
16.1
.0
-15
60
88
Analog main menu
Analog submenu shows
Initial interface
Analog ID definitions
F01: The maximum pressure between the
F02: Pressure 1
F03: Pressure 2
F04: Ambient temperature
F05: SCR temperature
F06: Output voltage percentage
pressure 1 and pressure 2; 88.8 will be
shown when the pressure sensor is disabled
the ID and values circulary
- -
Current alarm main interface
Press the ENT key to enter the current alarm submenu interface when the current main interface shows
‘A--’ (the
symbol of current alarm main menu). The switching operation processes and orders of the current alarm submenu are
shown in the following figure.
See Table 6-3 for generating conditions and troubleshooting.
No alarm
Current alarm main
ENT key
ESC key
UP key
DOWN key
Current alarm ID definitions
A00: Phase loss alarm
A01: SCR over temperature
A02: Fan 1 over temperature
A03: Fan 2 over temperature
A04: Pressure sensor failure
A05: EEPROM read fault
A06: SCR temperature sensor failure
A07: Abnormal frequency
A
F
- - -
AXX
AXX
AXX
AXX
or
When there is an alarm, the XX of
menu interface
alarm ID is the number from 00
- -
- -