Licht
http://www.licht-labs.com
Rev. A1 (20–05–09) MFC-400/I-IAC and I-IDC Technical Manual
6
Parameter
:
Format
Options
: 8N1, 8E1, 8O1, 8N2.
Description
: symbol transmission format, where:
◦
8N1
: 8 data bits, no parity, 1 stop bit.
◦
8E1
: 8 data bits, even parity, 1 stop bit.
◦
8O1
: 8 data bits, odd parity, 1 stop bit.
◦
8N2
: 8 data bits, no parity, 2 stop bits.
Parameter
:
Address
Options
: 1 to 247.
Description
: MODBUS address for the MFC-400/I-IAC or MFC-400/I-IDC.
4.4 DNP3 protocol (option)
Parameter
:
Baud Rate
Options
: 9600, 19200, 38400, 57600, 115200 bps.
Description
: baud rate for the RS-485 link.
Parameter
:
Format
Options
: 8N1, 8E1, 8O1, 8N2.
Description
: symbol transmission format, where:
◦
8N1
: 8 data bits, no parity, 1 stop bit.
◦
8E1
: 8 data bits, even parity, 1 stop bit.
◦
8O1
: 8 data bits, odd parity, 1 stop bit.
◦
8N2
: 8 data bits, no parity, 2 stop bits.
Parameter
:
Address
Options
: 0x0000 to 0xFFEF.
Description
: DNP3 outstation address in hexadecimal notation.
Parameter
:
Application Layer Confirmation
Options
: Only when transmitting events or multi-fragment responses, Always.
Description
: Selects when the MFC-400 outstation should request application layer
confirmations.
Parameter
:
Maximum Inter-Octet Gap
Options
: 2 to 100 ms.