Liberty Pumps XLE100 Series Installation Manual Download Page 3

3473000C

Copyright © Liberty Pumps, Inc. 2021 All rights reserved.

3 | EN

This product requires a separate, properly fused and 

grounded branch circuit, sized for the voltage and amperage 

requirements of the pump, as noted on the nameplate. 

Overloaded branch circuit wires will get very hot and can 

catch on fire. When used, electrical outlets shall be simplex of 

the appropriate rating.

Sewage and effluent systems produce and may contain 

flammable and explosive gases. Prevent introduction of 

foreign objects into basin as sparks could ignite these gases. 

Exercise caution using tools and do not use electronic devices 

or have live, exposed electrical circuits in or around basins, 

open covers and vents.

Hazardous locations contain explosive gases that can be 

detonated by sparking or electric shock.

All terminations and penetrations of conduit or cable shall be 

done using approved materials and methods intended for use 

to mitigate the potential for explosion.

When working in a hazardous location, all precautions to 

minimize ignition sources such as spark and flame should be 

taken to limit the potential for fire or explosion. 

Use only non-sparking tools and components in and around 

basins, open covers and vents. Do not use electronic devices 

that are not rated for use in hazardous locations or have live, 

exposed electrical circuits in or around basins, open covers 

and vents. Sewage and effluent systems produce and may 

contain flammable and explosive gases and sparks could 

ignite these gases. 

Energizing the control panel or breaker for the first time is 

potentially dangerous. Licensed electrical personnel should 

be present when the panel or breaker is energized for the first 

time. If faults caused by damage or poor installation practices 

have not been detected, serious damage, injury or death can 

result when power is applied.

All electrical and motor repairs and service must be 

performed by a repair facility approved by Liberty Pumps and 

certified to work on explosion-proof motor enclosures.

Do not remove power supply or control cord. All electrical and 

motor repairs and service must be performed by the factory 

or a repair facility approved by Liberty Pumps and certified to 

work on explosion-proof motor enclosures.

Refer to Chapter 5 of the National Electric Code

®

 or 

applicable local codes and ordinances for all electrical and 

wiring requirements in hazardous locations.

Float switches must be connected to an intrinsically safe 

circuit in the control panel as per the requirements of 

Chapter 5 of the National Electric Code®.

All personnel shall be trained and qualified for safe work 

practices and procedures.

All installations shall be in compliance with all applicable 

Federal, State, and Local codes and ordinances for hazardous 

locations.

All electrical terminations shall be made according to Federal, 

State, and Local codes for hazardous or classified locations.

Conduit, junction boxes, and associated components shall be 

approved for use with hazardous locations and installed 

according to specifications.

Do not modify the pump/pump system in any way. 

Modifications may affect seals, change the electrical loading 

of the pump, or damage the pump and its components.

Do not allow children to play with the pump system.

Do not allow any person who is unqualified to have contact 

with this pump system. Any person who is unaware of the 

dangers of this pump system, or has not read this manual, can 

easily be injured by the pump system.

All pump/pump system installations shall be in compliance 

with all applicable Federal, State, and Local codes and 

ordinances.

In 208/230V installations, one side of the line going to the 

pump is always “hot”, whether the float switch is on or off. To 

avoid hazards, install a double pole disconnect near the pump 

installation.

Vent basin in accordance with local code. Proper venting of 

sewer and effluent gases alleviates poisonous gas buildup 

and reduces the risk of explosion and fire from these 

flammable gases.

Wear adequate Personal Protective Equipment when working 

on pumps or piping that have been exposed to wastewater. 

Sump and sewage pumps often handle materials that can 

transmit illness or disease upon contact with skin and other 

tissues.

Do not remove any tags or labels from the pump or its cord.

Do not enter a pump basin after it has been used. Sewage and 

effluent can emit several gases that are poisonous.

Keep clear of suction and discharge openings. To prevent 

injury, never insert fingers into pump while it is connected to 

a power source.

This product contains chemicals known to the State of 

California to cause cancer and birth defects or other 

reproductive harm. www.p65warnings.ca.gov.

This pump has been evaluated for use with water only, 

however use with human waste and toilet paper is permitted.

Check 3-phase pumps for correct rotation prior to installing 

pump(s) in basin. To change rotation, reverse any two of the 

three power leads to the pump (not the ground). Code the 

wires for reconnection after installation. 

Do not dispose of materials such as paint thinner or other 

chemicals down drains. Doing so could chemically attack and 

damage pump system components and cause product 

malfunction or failure.

Do not use pumps with fluid over 104°F (40°C). Operating the 

pump in fluid above this temperature can overheat the pump, 

resulting in pump failure.

Do not use pump system with mud, sand, cement, 

hydrocarbons, grease, or chemicals. Pump and system 

components can be damaged from these items causing 

product malfunction or failure. Additionally, flooding can 

occur if these items jam the impeller or piping.

RISK OF SERIOUS INJURY OR DEATH

Summary of Contents for XLE100 Series

Page 1: ...rence For replacement manual visit LibertyPumps com or contact Liberty Pumps at 1 800 543 2550 Retain dated sales receipt for warranty Model 7000 Apple Tree Avenue Bergen NY 14416 ph 1 800 543 2550 fa...

Page 2: ...res inside the power cord The electrical power supply shall be located within the length limitations of the pump power cord and for below grade installations it shall be at least 4 ft 1 22 m above flo...

Page 3: ...te and Local codes and ordinances for hazardous locations All electrical terminations shall be made according to Federal State and Local codes for hazardous or classified locations Conduit junction bo...

Page 4: ...complete If storage is necessary the pump should remain in its shipping container It should be stored in a warehouse or storage shed that has a clean dry temperature stable environment where the pump...

Page 5: ...rly sized or adjusted for the full load input power indicated on the pump nameplate It is important to properly select and adjust the motor control overload protection The full load amperes on the nam...

Page 6: ...e pump has cooled 1 phase models automatically reset after the pump has cooled to a safe temperature Power and Control Cords Do not remove cord and strain relief and do not connect conduit to pump The...

Page 7: ...into the pump intake The pump can remain upright or can be laid down on its side for easier access to the intake Besides verification that the impeller is freely spinning rotating the impeller helps t...

Page 8: ...skets and components are present Pump Record information from pump nameplate onto inside cover of these instructions Complete a visual inspection before lowering into basin Place pump in basin making...

Page 9: ...further assistance To keep the pump pump system operating smoothly perform the following routine checks Monthly Pumps that are idle for more than a month in a dry basin should have impellers manually...

Page 10: ...s trip Unintentional ground Turn off power and check motor leads for possible ground 3 phase motor winding failure Check resistance of motor windings All three phases should have the same reading Obst...

Page 11: ...pen gate or ball valve Total head is beyond pump s capability Route piping to a lower level If not possible a larger pump may be required Consult Liberty Pumps Obstructed impeller or volute clogged in...

Page 12: ...mages including costs of removal reinstallation or transportation There is no other express warranty All implied warranties including those of merchantability and fitness for a particular purpose are...

Reviews: