Liberty Pumps ProVore PRG Series Installation Manual Download Page 8

8 | EN

Copyright © Liberty Pumps, Inc. 2020 All rights reserved.

2399000D

 Electrical Connections

With main power disconnected, complete pump and control 

wiring connections per manufacturer’s wiring diagrams included 

with the control panel as applicable. Once wiring is complete, 

check all wires for unintentional grounds.

 Pump

Record information from pump nameplate onto inside cover of 

these instructions. Complete a visual inspection before lowering 

into basin.
Place pump in basin being sure the mounting interface (i.e., 

torque stop) is engaged correctly.

 Discharge

Make all discharge connections. A check valve is required to 

prevent the backflow of liquid after each pumping cycle. A gate 

valve should follow the check valve to allow periodic cleaning of 

the check valve or removal of the pump. The remainder of the 

discharge line should be as short as possible with a minimum 

number of turns to minimize friction head loss. Do not reduce the 

discharge to below the pump outlet size. Larger pipe sizes may be 

required to eliminate friction head loss over long runs. Contact 

Liberty Pumps or other qualified person if questions arise 

regarding proper pipe size and flow rates.

 Vent

Vent basin in accordance with applicable plumbing codes.

 Automatic Pump Direct Wiring

 

In 208/230V installations, one side of the line going to the 

pump is always “hot”, whether the float switch is on or off. To 

avoid hazards, install a double pole disconnect near the pump 

installation.

 

If the pump will be wired directly into a control device or junction 

box, it is necessary to remove the plug. Qualified personnel shall 

complete the wiring in accordance with the National Electric Code 

and applicable local codes. A disconnecting means for the pump 

shall be located in sight from the pump/basin location. See 

Figure 2 for direct wire installation of automatic pumps.

 Figure 2. Direct Wiring of Automatic Pumps

 Piggyback Switch Operation

 

Single-phase 208/230V pumps shall only be operated without 

the float switch by using the circuit breaker or panel 

disconnect.

 

Some products may have internal capacitors that could cause 

shock. Avoid contact with plug ends after removing from 

energy source.

 

For automatic operation

, the two cords should be interconnected 

and plugged into a separately fused, grounded outlet of proper 

amp capacity for the selected pump model. Both cords are 

equipped with 3-prong plugs and must be plugged into a 

properly grounded 3-wire receptacle. 

Do not remove the ground 

prongs.
For manual operation

, or in the event of switch failure, the pump 

cord can be separated and plugged into the electrical outlet 

directly, bypassing the switch and using the circuit breaker or 

panel disconnect to operate the pump.

 Figure 3. Piggyback Switch Operation

Operation

 

 

Energizing the control panel or breaker for the first time is 

potentially dangerous. Licensed electrical personnel should 

be present when the panel or breaker is energized for the first 

time. If faults caused by damage or poor installation practices 

have not been detected, serious damage, injury or death can 

result when power is applied.

 

 Starting System

1.

Verify all plumbing components in the basin are installed 

correctly and functional. Verify all valves are open and ready 

for pump use.

2.

Double check all wire connections. Re-tighten all factory and 

field connections.

3.

Ensure pump has no obstructions.

4.

With all electrical and mechanical connections complete and 

secure, turn on power to pump and control panel, if 

applicable.

5.

Verify operation of the pump, floats, and alarm circuits.

6.

Run several cycles of water through the system to verify 

correct control operation for the installation.

Be certain to complete adequate testing, especially on systems 

with multiple pumps or custom control configurations.

RISK OF SERIOUS INJURY OR DEATH

Ground

Black

Junction Box

Power

Supply

White

Float

Switch

Pump

Green

Black

White

Green

Black

White

RISK OF ELECTRIC SHOCK

RISK OF SERIOUS INJURY OR DEATH

Temporary Manual

Operation

 

YES!

NO!

Summary of Contents for ProVore PRG Series

Page 1: ...www LibertyPumps com Keep this manual handy for future reference For replacement manual visit LibertyPumps com or contact Liberty Pumps at 800 543 2550 Retain dated sales receipt for warranty Serial...

Page 2: ...ly live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power cord and for below grade installations it shall be at least 4 ft 1 22 m...

Page 3: ...ho is unaware of the dangers of this pump system or has not read this manual can easily be injured by the pump system In 208 230V installations one side of the line going to the pump is always hot whe...

Page 4: ...n one month should have cutters and impellers manually operated through the breaker panel once a month to lubricate the seals For automatic models turn off the breaker unplug the piggyback switch and...

Page 5: ...odels Automatic models A suffix come factory equipped with a float switch mounted to the pump These models come with two cords one to the float switch and the other to the pump motor The float switch...

Page 6: ...lumbing is below the frost line If this is not feasible remove the check valve and size the basin and or adjust pump differential to accommodate the additional backflow volume Consult Liberty Pumps fo...

Page 7: ...on operational for more than a week It is recommended to rotate the cutter 5 10 full rotations Installation All installation and maintenance of pumps controls protection devices and general wiring sha...

Page 8: ...k Switch Operation Single phase 208 230V pumps shall only be operated without the float switch by using the circuit breaker or panel disconnect Some products may have internal capacitors that could ca...

Page 9: ...ers automatically voids warranty RISK OF ELECTRIC SHOCK RISK OF SERIOUS INJURY OR DEATH Table 2 Troubleshooting Matrix Problem Possible Cause Corrective Action Pump does not start Damaged power or con...

Page 10: ...mp does not deliver proper capacity Discharge valve s partially closed or clogged Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Ch...

Page 11: ...vity Clean the impeller cavity Repeated tripping Circuit protection underrated Check rating and replace with proper size Other appliance on same circuit Pump requires separate circuit Pump is connecte...

Page 12: ...operated or maintained per manufacturer instructions if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been...

Reviews: