 Pump Control and Alarm Floats

The engineering drawings will generally specify the levels for 

Pump ON, Pump OFF, and High Level alarm. If they are not 

specified, the guidelines in Table 1 should be used to determine 

float switch locations. The upper water level should be positioned 

to minimize pump starts. The High Level alarm float must be 

above the Pump ON float but below any inlets. No float should be 

set above the inlet to the basin.

 Cutter and Impeller Free Movement Check

Wear Personal Protective Equipment as exposed bottom has 

sharp edges.

Do not connect any power to pump until this check is complete. 

Manually rotate the cutter to check that it spins freely with very 

little resistance. The cutter is located on the bottom of the pump. 

The cutter can be carefully rotated by hand, or rotated by 

inserting a tool into the cutter bolt. If rotating by hand, wear 

protective gloves as the cutter and cutter plate have sharp edges. 

The pump can remain upright or can be laid down on its side for 

easier access to the cutter. Besides verification that the cutter and 

impeller are freely spinning, rotating the cutter helps to lubricate 

the shaft seals if the pump has been non-operational for more 

than a week. It is recommended to rotate the cutter 5–10 full 

rotations.

Installation

 

All installation and maintenance of pumps, controls, 

protection devices, and general wiring shall be done by 

qualified personnel.

 

All electrical and safety practices shall be in accordance with 

the National Electrical Code

®

, the Occupational Safety and 

Health Administration, or applicable local codes and 

ordinances.

 

Figure 1 shows a typical installation. Variations may apply to 

actual installation.

 Figure 1. Typical Indoor Installation (Pro380-Series shown)

Table 1. Float Switch Settings

System

Float

Levels

Piggyback Switch

(1-Float System, 

Wide-Angle)

Pump OFF

Factory set.

3-1/2” float tether.

Pump ON

Factory set.

3-1/2” float tether.

Piggyback Switch

(1-Float System, 

Vertical)

Pump OFF

Factory set.

2” from bottom of 

float rod.

Pump ON

Maximum travel on 

float rod.

Simplex Pump 

Station

(3-Float System)

Pump OFF

Level to top of motor 

housing.

Pump ON

Minimum 1-1/2’ above 

Pump OFF level.

High Level

Minimum 1’ above 

Pump ON level and 

below inlet pipe. Below 

influent pipe.

Duplex Pump 

Station

(4-Float System)

Pump OFF

Level to top of motor 

housing.

Lead Pump ON

Minimum 1-1/2’ above 

Pump OFF level.

Lag Pump ON

Minimum 1’ above 

Lead Pump ON level.

High Level

Minimum 1’ above Lag 

Pump ON level and 

below inlet pipe. Below 

influent pipe.

RISK OF ELECTRIC SHOCK

Alarm

(optional)

Vent

Union

Check Valve

Ball Valve

Discharge

Use No-hub Style 

Connector 4" Inlet Pipe

Summary of Contents for ProVore PRG Series

Page 1: ...www LibertyPumps com Keep this manual handy for future reference For replacement manual visit LibertyPumps com or contact Liberty Pumps at 800 543 2550 Retain dated sales receipt for warranty Serial...

Page 2: ...ly live wires inside the power cord The electrical power supply shall be located within the length limitations of the pump power cord and for below grade installations it shall be at least 4 ft 1 22 m...

Page 3: ...ho is unaware of the dangers of this pump system or has not read this manual can easily be injured by the pump system In 208 230V installations one side of the line going to the pump is always hot whe...

Page 4: ...n one month should have cutters and impellers manually operated through the breaker panel once a month to lubricate the seals For automatic models turn off the breaker unplug the piggyback switch and...

Page 5: ...odels Automatic models A suffix come factory equipped with a float switch mounted to the pump These models come with two cords one to the float switch and the other to the pump motor The float switch...

Page 6: ...lumbing is below the frost line If this is not feasible remove the check valve and size the basin and or adjust pump differential to accommodate the additional backflow volume Consult Liberty Pumps fo...

Page 7: ...on operational for more than a week It is recommended to rotate the cutter 5 10 full rotations Installation All installation and maintenance of pumps controls protection devices and general wiring sha...

Page 8: ...k Switch Operation Single phase 208 230V pumps shall only be operated without the float switch by using the circuit breaker or panel disconnect Some products may have internal capacitors that could ca...

Page 9: ...ers automatically voids warranty RISK OF ELECTRIC SHOCK RISK OF SERIOUS INJURY OR DEATH Table 2 Troubleshooting Matrix Problem Possible Cause Corrective Action Pump does not start Damaged power or con...

Page 10: ...mp does not deliver proper capacity Discharge valve s partially closed or clogged Check the discharge line for foreign material including ice if the discharge line passes through or into cold areas Ch...

Page 11: ...vity Clean the impeller cavity Repeated tripping Circuit protection underrated Check rating and replace with proper size Other appliance on same circuit Pump requires separate circuit Pump is connecte...

Page 12: ...operated or maintained per manufacturer instructions if it has been disassembled modified abused or tampered with if the electrical cord has been cut damaged or spliced if the pump discharge has been...