©Copyright 2016 Liberty Pumps Inc. All rights reserved 6
Control Panel Terminal Block
Six-Float system:
Connect all six floats to the appropriate terminals (i.e. lowest float to terminals 3 &
4 for the STOP float)
Five-Float system:
Connect floats to the appropriate terminals for STOP, LEAD, LAG1, LAG2, and
LAG3. Use a jumper wire to connect terminals 12 and 14 to trigger the alarm when the highest float
is activated.
Four-Float system:
Connect floats to the appropriate terminals for STOP, LEAD, LAG2, and
ALARM. Use a jumper wire to connect terminals 6 and 8 to always operate two pumps when the lead
pump is triggered. Use another jumper wire to connect terminals 10 and 12 to always operate a
separate pare of pumps when a lag pump is triggered.
Three-Float system:
Connect floats to the appropriate terminals for STOP, LEAD, and LAG2. Use
a jumper wire to connect terminals 6 and 8 to always operate two pumps when the lead pump is
triggered. Use another jumper wire to connect terminals 10 and 12 to always operate a separate
pare of pumps when a lag pump is triggered. Use another jumper wire to connect terminals 12 to 14
to activate an alarm when the lag pumps are triggered.