Liberty Pumps LCU-N Series Installation Manual Download Page 3

4196000A

Copyright © Liberty Pumps, Inc. 2021 All rights reserved.

3 | EN

Do not dispose of materials such as paint thinner or other 

chemicals down drains. Doing so could chemically attack and 

damage pump system components and cause product 

malfunction or failure.

Do not use pumps with fluid over 150°F (65°C). Operating the 

pump in fluid above this temperature can overheat the pump, 

resulting in pump failure.

Do not use pump system with mud, sand, cement, 

hydrocarbons, grease, or chemicals. Pump and system 

components can be damaged from these items causing 

product malfunction or failure. Additionally, flooding can 

occur if these items jam the impeller or piping.

Do not allow pump to freeze.

General Information

Before Installation, read the following instructions carefully. Each 

Liberty Pumps product is individually factory tested to assure 

proper performance. By closely following these instructions, 

potential operating problems should be eliminated, providing 

years of trouble-free service.

Installation

A.

Select a location that is level and below the condensate pan 

drain. The unit may be mounted on a wall by using the 

mounting tabs on the tank, which are 17.6” apart. 

B.

Connect the drain pan. Use vinyl tubing, PVC, or any other 

suitable material. Be sure the tubing or pipe extends into the 

inlet of the tank by at least 1".
Connect as follows:

STANDARD

 condensate (dehumidifiers, A/C, etc.) can be 

connected to any of the three intake holes (1), (2), (3). 

ACIDIC

 condensate (high-efficiency boilers and furnaces) 

must be installed in inlet (4) or (5).

C.

The discharge connection to the check valve may be made 

with 3/8” vinyl tubing secured by a hose clamp (not included), 

or the barb may be removed by sawing so that threaded 

fittings may be attached. The thread is 1/4” NPT. 
Connect discharge hose or pipe to the pump. 

Only 

hand-tighten discharge fasteners.

 Over-tightening may cause 

the discharge housing to crack and leak. Once the discharge 

tubing has been extended to the required height it should be 

slanted downward, if possible, to assist in drainage. 

Note

: For 

best results, do not extend discharge tubing beyond 17' 

vertically.

D.

The safety switch leads should be connected to a Class 2 low 

voltage circuit (not to exceed 30 volts). Using this feature may 

prevent damage from condensation overflowing if the 

discharge becomes blocked or if the pump fails. The leads 

may be connected in series with the low voltage thermostat 

circuit so as to shut down the heating/air-conditioning 

system if the water level in the pump tank rises beyond 

normal, or they may be connected to an external alarm.

E.

If necessary, the pump unit may be removed and rotated 180° 

to make access to the plumbing inlet and discharge lines 

easier. To rotate the pump:
1. Remove the clear neutralization chamber cover by 

inserting a screwdriver in the slot and prying the tank 

outward.

2. Remove the pump unit using the same process.
3. Rotate the pump, and snap it back into place.
4. Snap the neutralization chamber cover back in its initial 

position.

F.

When all mounting and water connections are secure, 

connect the unit to an electrical supply. Disconnect electrical 

power at fuse or circuit breaker box before making any 

connections. The power cord must be connected to a 

constant source of power (not a fan or other device that runs 

intermittently) matching the voltage specified on the pump 

nameplate.
If connecting a pump with a stripped wire cord end, power 

connections must be made within a junction box or 

appropriate enclosure and must comply with the NEC and 

any applicable codes. Wiring is as follows: GREEN is ground, 

BLACK is line, and WHITE is neutral (115V) or line2 (230V).

G.

To ensure proper installation, energize power and test the 

unit by adding water to the tank until the pump activates. Be 

sure the water discharges properly. Finally, check the 

connections for leakage and proper discharge pipe routing.

Maintenance and Troubleshooting

 

Accidental contact with electrically live parts, items, fluid, or 

water can cause serious injury or death.

 

Always disconnect the pump from power source before 

attempting to service the pump. Fatal electrical shock could 

occur.

  

 Maintenance

Pump models have sealed permanently lubricated bearings and 

require no additional lubrication.

 Quarterly 

Check the outlet pH level using a pH strip or electronic pH meter. 

The cartridge kit must be replaced the sooner of (1) annually or (2) 

if the pH at the outlet drops below 5.0 (or the minimum level of 

the local water authority). Use 

only

 Liberty Pumps replacement 

cartridge kit #K001898. To replace the neutralization cartridge, 

remove the neutralization chamber cover, exchange the cartridge 

and replace cover.
Inspect the condensate pump tank to ensure it is free of 

accumulated dirt or sludge. 

Do not

 

use solvent cleaners. Clean 

tank with mild soap and warm water only. Clean inlet and outlet 

piping. Reassemble system and check for correct operation.
Pour enough water into the tank to activate the pump when not 

normally in use.

 As Needed 

If unit is mounted in an unheated area that is exposed to 

temperatures below freezing, the unit and lines must be drained 

to prevent damage to the pump.

Standard condensate inlet (

1

), (

2

), or (

3

)

Acidic condensate inlet (

4

) or (

5

) only

TOP VIEW

1

2

5

3

4

RISK OF ELECTRIC SHOCK

Reviews: