10
INSTALLATION OF OUTDOOR UNIT
ENGLISH
1
DIP_SW Setting
Set the DIP_SW as below Table (
Ⓐ
)
2
Auto Addressing Method
Addressing work assigns address to each indoor unit. When firstly installing product or replac-
ing the indoor unit PCB. Auto Addressing work should be done for simultaneous operation.
* Work procedure
1) Set DIP_SW correctly.
2) Turn on main power.
3) Press the SW01M for about 3 seconds within 3 minutes After main power on.(
Ⓑ
)
4) After step 3), the LED01E(red LED) and LED02E(green LED) rapidly flickers. When Addressing
work is done, green LED is off, else LED (LED01E) stops flickering and lights continuously. Ad-
dress of indoor unit is indicated on the wired remote control display window. (CH01, CH02,
CH03, CH04)
5) Press
]
button to turn on the indoor.
6) If you fail to perform the Addressing work, repeat step 2)~5).
Outdoor Unit PCB Setting Procedure For Simultaneous Operation System
Main PCB
SW01M
DIP S
W
0
1D
A
B
LED01E
LED02E
12
3
4
5
6
7
8
9
10
DIP SW01D
Indoor Unit No.
1
2
3
4
5
6
7
8
9
10
1(Single)
: Default
1
2
3
4
5
6
7
8
9
10
2(Duo)
1
2
3
4
5
6
7
8
9
10
3(Trio)
1
2
3
4
5
6
7
8
9
10
4(Quartet)
1,MFL68645301(영) 2017. 6. 16. 영영 1:43 Page 10