Installation Manual
23
ENGLISH
How to Set E.S.P?
• If you set ESP incorrectly, the air conditioner may malfunction.
• This setting must be carried out by a certificated-technician.
This is the function that decides the strength of the wind for each wind level and because this function
is to make the installation easier.
Installer Setting - E.S.P.
If entering into ESP setup mode by using
button, it indicates as the picture
below.
2
Select ESP fan step by
pressing button.
(01: very low, 02: low, 03:
medium, 04: high, 05:
very high)
3
Move to ESP value setting by pressing
button.
(It is 000 when delivering
from the warehouse.)
4
Press button to setup ESP value.
(It is possible to setup ESP
value from 1 to 255, and 1 is
the smallest and 255 is the
biggest.)
5
If pressing button long for 3
seconds, it enters into remote
controller setter setup mode.
- If pressing once shortly, it enters
into user setup mode. Please press
more than 3 seconds for sure.
1
Function Code
ESP value
ESP step
Press button to save.
7
Select ESP fan step again by using
button and setup ESP value, as No. 4
and 5, that corresponds each wind flow
6
Press button to exit.
❈
After setup, it automatically gets out of
setup mode if there is no button input
for 25 seconds.
❈
When exiting without pressing set
button, the manipulated value is not
reflected.
8
Function code,
ESP code
ESP value
• When setting ESP value on the product without very weak wind or power wind function,
it may not work.• Please be careful not to change the ESP value for each fan step.
• It does not work to setup ESP value for very low/power step for some products.
• ESP value is available for specific range belongs to the product.
How to Set E.S.P?