![LG TBNC096TSG0 Installation Instructions Manual Download Page 5](http://html.mh-extra.com/html/lg/tbnc096tsg0/tbnc096tsg0_installation-instructions-manual_1892395005.webp)
H
SI
L
G
N
E
2. Indoor unit installation
■
Installation of Unit
Install the unit above the ceiling correctly.
• Apply a joint-canvas between the unit and
duct to absorb unnecessary vibration.
• Apply a filter Accessory at air return hole.
• Install the unit leaning to a drainage hole
side as a figure for easy water drainage.
• A place where the unit will be leveled and
that can support the weight of the unit.
• A place where the unit can withstand its
vibration.
• A place where service can be easily
performed.
5
CASE 1
POSITION OF SUSPENSION BOLT
CASE 2
POSITION OF CONSOLE BOLT
(Unit:mm)
Top
Front
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4 (Local
supply)
X 4
M10 Nut
M10 SP. washer
M10 washer
X 4
X 4 (Local
supply)
X 4
708
678
434
51
537
525
230
1058 1028
434
51
537
875
230
1258 1228
434
51
537
1075
230
1552 1605
441
47.5
537
1422
270
Capacity
Dimension
8K/9K/12K
18K
24K
42K
Btu/h
G