Setting and Using Method
Installation manual
23
7. Setting Example
Using
Demand control
Using Demand control function with 3-Non Voltage contact.
Input_1
Input_2
Input_3
Input_LNO
Reserved Reserved
LG does not supply this section
(Field supply)
With this function comp capacity of outside unit can be controlled.
Ex) Demand control by 3-contact signal
SW_ STEP
Input_1
Input_2
Input_3
Comp capacity Of outside
unit(%)
Type of input
0
0
0
0
No control
Contact signal
1
0
0
70
0
1
0
40
0
0
1
Comp off
CAUTION
• This input can accept only non voltage contact.
Do not input external power source. Otherwise it will cause a serious damage.