AI
10-2
0
0
0.4
Comp.
off
-
-
-
-
DO 01-4 is short,
DO 01-2 is open.
1
0.6
1.4
Comp.
off
-
-
-
-
2
1.6
2.4
40
1,160
20.3
1,800
28.4
DI will determine
fan mode and
opeation mode
3
2.6
3.4
45
1,100
19.0
1,950
31.5
4
3.6
4.4
50
1,070 17.9
2,080
34.1
5
4.6
5.4
60
990
15.8
2,340
38.9
6
5.6
6.4
70
930
14.0
2,560
42.5
7
6.6
7.4
80
870
12.5
2,730
45.1
8
7.6
8.4
90
830
11.3
2,990
49.0
9
8.6
9.4
100
800
10.5
3,000
49.2
10
9.6
10
100
800
10.5
3,000
49.2
AHU KIT WIRING CONFIGURATION WITH DDC
27
ENGLISH
AI
No.
Input
voltage
[Vdc]
Low
[Vdc]
High
[Vdc]
Capacity
of unit
[%]
Cooling
Heating
Control
Target
Low
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
Target
High
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
AI
No.
Input
voltage
[Vdc]
Low
[Vdc]
High
[Vdc]
Capacity
of unit
[%]
Cooling
Heating
Control
Target
Low
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
Target
High
Pressure
[kPa]
Tempera-
ture at
HEX [°C]
2. Option #2
3. Option #3
AI
10-2
0
0
0.4
Comp.
off
-
-
-
-
DO 01-4 is short,
DO 01-2 is open.
1
0.6
1.4
40
1160
20.3
1800
28.4
DI will determine
fan mode and
opeation mode
2
1.6
2.4
45
1100
19.0
1950
31.5
3
2.6
3.4
50
1070
17.9
2080
34.1
4
3.6
4.4
60
990
15.8
2340
38.9
5
4.6
5.4
70
930
14.0
2560
42.5
6
5.6
6.4
80
870
12.5
2730
45.1
7
6.6
7.4
90
830
11.3
2990
49.0
8
7.6
8.4
100
800
10.5
3000
49.2
9
8.6
9.4
100
800
10.5
3000
49.2
10
9.6
10
100
800
10.5
3000
49.2