8
Wired Remote Controller
<Installer Setting Code Table>
1) General air-conditioner product
j
Some contents may not be displayed depending on the product function
Installation instruction
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user injury or property
damage. This must be set by an certificated installer, and any installation or change that is carried out by a
non-certificated person should be responsible for the results. In this case, free service cannot be provided.
CAUTION
Installer Setting -How to enter installer setting mode
TEMP
FAN
SPEED
OPER
MODE
Function Code
Value
If you want to set installer setting mode, Press
the Temperature up button and the oper mode
button same time for five seconds.
1
When you enter the setting mode
Initially. Function code is displayed
on the LCD screen.
2
No.
Function
Code
Value
1
Test Run
01
01:Set
2
Address Setting
02
00~FF : Address
<ESP Step>
<ESP Value>
<Example>
01:VeryLow
0 ~ 255
02:Low
3
E.S.P. Value
03
03:Med
04:High
05:Very High
01:Remo
4
Thermistor
04
02:Indoor
03:2TH
01:Med
02:Low
5
Ceiling Height
05
03:High
04:Very High
01:V-H
02:F-H
6
Static Pressure
06
03:V-L
04:F-L
7
Master Setting
07
00:Slave
01:Master
8
Celsius
12
00:Celsius
(Optimized only for U.S.A)
Fahrenheit Switching
01:Fahrenheit
Function Code
ESP value
ESP step