Setting and using method
18
Dry contact for demand control
7. Setting of ʻSW_Addressʼ
I
Use the ʻSW_Addressʼ to set an address of outdoor unit
- Master Mode
use SW_ADDRESS2 to set a group(0~F)
If you set a group as “0”, the address of outdoor unit should be “00~0F”
- Slave Mode (when using with central control device)
use all to set the address of outdoor unit for sending to central control device.
Notes
• Using this switch, the address of outdoor unit can be set as 0~254(00~FE)
• If the outdoor unit has itʼs own address, you need not to set address in slave mode.
• After change ʻSW_Adressʼ setting, then you must press reset switch to reflect the setting.
SW_
ADDRESS2
SW_
ADDRESS1
Outdoor address setting
Address : 0 0
SW_Address2
SW_Address1