Installation Guide
8
485 Gateway(M)
ON
1
2
3
4
5
6
7
8
Select Air
Conditioer Type
Select Network Type
Select Advanced Control Type
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
ON
DIP Switch Configuration
* LGAP : LG Air conditioner Protocol
‘
1 ON, All others OFF
: Multi V products(Except CRUN products) or
Multi(Non-Inverter) Product applied Common PCB(Refer to NOTE) or
Multi(Inverter) P Central Controller(All types) - Without LGAP
‘
1 and 4 ON, All others OFF
: Multi V products(Except CRUN products) or
Multi(Non-Inverter) Product applied Common PCB or Multi(Inverter) P
Central Controller(All types) - Using LGAP
‘
2 ON, All others OFF
: Multi(Non-Inverter) Product
+ Centroller(All types) - Without LGAP
‘
2 and 4 ON, All others OFF
: Multi Non-Inverter Product
+ Central Controller(All Types) - Using LGAP
‘
1,2,3,4 ON
: Multi V CRUN Product
+ Central Controller(All types) - Using LGAP
Multi V & Multi(LGAP applied) products Configuration Methods
CAUTION:
The wrong setting of air-conditioner switch could cause malfunctioning.
Switch setting must be done carefully.
Push the Reset button after changing the Dip switch.
NOTE:
Multi(Non-Inverter) Product applied Common PCB
PCB P/NO. : 6871A20917*
P/NO. : 6871A20918*
P/NO. : 6871A20910*
* Please refer the corresponding Central Controller installation manual if you want to know whether
your Central Controller is compatible with LGAP or not.
Summary of Contents for PMNFP14A0
Page 10: ...10 485 Gateway M ...
Page 20: ...10 485 Gateway M ...
Page 30: ...10 485 Gateway M ...
Page 40: ...10 Interface 485 M ...
Page 50: ...10 485 Gateway M ...
Page 60: ...10 485 Πύλη M ...
Page 70: ...10 Passagem 485 M ...
Page 80: ...10 485 Gateway M ...
Page 82: ...2 485 网关 M PI 485 安装手册 目 录 安全注意事项 3 4 部件说明 5 附件 6 安装指南 7 9 安装步骤 7 DIP 开关配置 8 高级锁定控制类型 9 ...
Page 86: ...6 485 网关 M 附件 附件 其它 扎带 3 EA 扎带夹 1 EA ON 1 2 3 4 5 6 7 8 ...
Page 90: ...10 485 网关 M ...