Installation manual
15
ENGLISH
Setting and using method
5. Installation of thermostat
■
When interlocking with thermostat, select the option of
control function as described below.
CHANGEOVER_SW
RESET_SW
CN_Ther/Oper
CN_MODE
CN_WIND
CN_INDOOR
DISPLAY_LED
TEMP_SW
SETTING_SW
CN_OUT
CN_PI485
SETTING_SW
TEMP_SW
<Switch Function>
TEMP_SW
SETTING_SW
Thermostat mode
WIND Signal en/disable
F
0
Conventional AC Unit Thermostat
Disable
1
Enable
2
Heat Pump Thermostat_O
Terminal
Disable
3
Enable
4
Heat Pump Thermostat_B
Terminal
Disable
5
Enable
1) When interlocking with thermostat, set TEMP_SW to F.
2) Enable CN_WIND signal – Amount of wind flow(Low, Middle, High) signal enable
Notes
• Information of ‘SETTING_SW’ is sensed only initial step by Dry contact module therefore , once the
configuration changed , Reset of Dry contact module is required.
• After power input or unit’s reset , wait 25~30 sec(Display LED 10 times blinking) for unit stabilization
then Dry contact module will operate normally.
• Do not use desired temperature setting function when interlocking with thermostat.