
Installation Manual
35
ENGLISH
System set-up
Ventilation information entry
Type
■
Master: Master Ventilation
■
Slave: Ventilation connected lower to the master
Units
■
Click on the ventilation window to add or edit and you will see the
yellow entry window where you can edit the name.
Address
■
Just like the air condition information entry, enter the G/W number,
outdoor unit number, individual ventilation number in order.
■
You can enter the physical address value for the master type
ventilation but for the save type ventilation, it must succeed the master
value and be automatically generated. (Cannot be entered)
■
When the ventilation is directly connected to G/W without going
through the outdoor unit, you must enter a "-" to the outdoor unit
number.
■
In installing ventilator , Set Ventilator address only [00] ~ [0F] by
ventilator wired remote controller
Because 1 CNU is connectable 16 ventilator(max)
■
The number on the farthest right is automatically set according to the
ventilation type.
(0 for master and 1, 2, 3.... for slave.)
Model
Default value
Set by each model.
Maximum power consumption
By setting the maximum power consumption value of the ventilation
system, the system limits the power consumption within the set limit.
Temporary save
It is convenient to use this function when moving the ventilation to
another group or changing the order of the ventilation.
When you save the master ventilation, the sub slave ventilation also
follows.
CAUTION
When saving the changes, the information in temporary save
will be deleted.