18
CONTROL
ENGLISH
Coil Register
No
Address
Register
Description
Range
Value explanation
HEX DEC
High
Low
1 0x0000
0
00001
Enable/Disable (Heating/Cooling)
1
0
0 : Operation OFF / 1 : Operation ON
2 0x0001
1
00002
Enable/Disable (DHW)
1
0
0 : Operation OFF / 1 : Operation ON
5 0x0004
4
00005
Emergency stop
1
0
0 : Normal operation /
1 : Emergency stop
Discrete Register
No
Address
Register
Description
Range
Value explanation
HEX DEC
High
Low
1 0x0000
0
10001
Water flow status
1
0
0 : Flow rate ok / 1 : Flow rate too low
2 0x0001
1
10002
Water pump status
1
0
0 : Water pump OFF /
1 : Water pump ON
4 0x0003
3
10004
Compressor status
1
0
0 : Compressor OFF /
1 : Compressor ON
5 0x0004
4
10005
Defrosting status
1
0
0 : Defrost OFF / 1 : Defrost ON
6 0x0005
5
10006
DHW heating status
(DHW Thermal On/Off)
1
0
0: DHW inactive / 1: DHW active
9 0x0008
8
10009
Cooling status
1
0
0 : No cooling / 1 : Cooling operation
14 0x000D 13
10014
Error status
1
0
0 : No error / 1 : Error state
Input Register
No
Address
Register
Description
Range
Value explanation
HEX DEC
High
Low
1 0x0000
0
30001
Error code
0xFFFF 0x0000
Error code
2 0x0001
1
30002
ODU operation cycle
0xFFFF 0x0000
0 : Standby(OFF) /
1 : Cooling / 2 : Heating
3 0x0002
2
30003
Water inlet temp.
0xFFFF 0x0000
[0.1 °C ×10]
4 0x0003
3
30004
Water outlet temp.
0xFFFF 0x0000
[0.1 °C ×10]
6 0x0005
5
30006
DHW tank water temp.
0xFFFF 0x0000
[0.1 °C ×10]
13 0x000C 12
30013
Outdoor air temp.
0xFFFF 0x0000
[0.1 °C ×10]
Holding Register
No
Address
Register
Description
Range
Value explanation
HEX DEC
High
Low
1 0x0000
0
40001
Operation mode
4
0
0 : Cooling / 4 : Heating / 3 : Auto
2 0x0001
1
40002
Control method
1
0
0 : Water outlet temp. control
1 : Water inlet temp. control
3 0x0002
2
40003
Target temp (Heating/Cooling)
65
5
°C
5 0x0004
4
40005
Shift value(Target) in auto mode
5
-5
1K
9 0x0008
8
40009
DHW target temp.
65
30
°C