How to Set E.S.P?
24
Indoor Unit
How to Set E.S.P?
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the
installation of the product. Otherwise, there is a risk of weak cooling/heating and
condensed water discharge/drop.
M1 Chassis : 7, 9, 12, 15, 18 k
M1 Chassis : 24 k
(Unit: CMM)
(Unit: CMM)
Setting
value
Static Pressure (mmAq(Pa))
2.5(25)
4(39)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
70
11.3
-
-
-
-
-
-
-
75
12.8
-
-
-
-
-
-
-
80
14.4
11.4
-
-
-
-
-
-
85
15.9
13.2
10.2
-
-
-
-
-
90
17.5
15.0
12.0
-
-
-
-
-
95
19.0
16.7
13.7
10.7
-
-
-
-
100
20.6
18.5
15.5
12.5
-
-
-
-
105
22.1
20.3
17.3
14.3
11.1
-
-
-
110
23.7
22.1
19.0
16.1
13.1
10.0
-
-
115
-
23.8
20.8
17.9
15.1
12.2
-
-
120
-
-
22.6
19.7
17.1
14.3
11.3
-
125
-
-
-
21.5
19.1
16.5
13.6
11.9
130
-
-
-
23.3
21.2
18.7
15.8
14.3
135
-
-
-
-
23.2
20.8
18.0
16.7
140
-
-
-
-
-
23.0
20.3
19.1
145
-
-
-
-
-
-
22.5
21.5
150
-
-
-
-
-
-
-
23.8
Setting
value
Static Pressure (mmAq(Pa))
2.5(25)
4(39)
6(59)
8(78)
10(98)
12(118)
14(137)
15(147)
85
16.8
14.6
-
-
-
-
-
-
90
18.1
15.9
-
-
-
-
-
-
95
19.4
17.2
15.0
-
-
-
-
-
100
20.7
18.5
16.3
13.9
-
-
-
-
105
22.0
19.8
17.7
15.3
13.0
-
-
-
110
23.3
21.1
19.1
16.8
14.6
-
-
-
115
24.6
22.4
20.5
18.3
16.3
14.2
-
-
120
25.9
23.7
21.8
19.7
17.9
15.9
13.3
-
125
-
25.1
23.2
21.2
19.6
17.5
15.2
14.6
130
-
-
24.6
22.7
21.2
19.2
17.1
16.3
135
-
-
-
24.2
22.9
20.9
19.0
18.1
140
-
-
-
-
24.5
22.6
20.9
19.9