48
PIPE CONNECTIONS BETWEEN INDOOR AND OUTDOOR UNIT
ENGLISH
This function is used for creating vacuum in the system after compressor replacement, ODU
parts replacement or IDU addition/replacement.
Vacuum mode setting method
Vacuum mode off method
CAUTION
!
ODU operation stops during vacuum mode. Compressor can't operate.
Master unit PCB DIP switch on : No.5
Select the mode using ‘
▶
’, ‘
◀
’ Button :
“SVC” Push the ‘
●
’ button
Select the Function using ‘
▶
’, ‘
◀
’ Button : :
“Se3” Push the ‘
●
’ button
Start the vacuum mode : “VACC”
ODU V/V open
ODU EEV open
IDU EEV open
DIP switch off and push the reset button on PCB
Vacuum Mode
DIP-SWITCH 7 - Segment
SW01C ( : confirm)
SW02C ( : backward)
SW03C ( : forward)
SW04C ( : cancel)
SW01D (reset)
SW01C ( : confirm)
SW04C ( : cancel)
DIP SWITCH
7-Segment
SW02C ( : backward)
SW01D (reset)
SW03C ( : forward)
(U3 / U7)
(U4)
Summary of Contents for Multi V S
Page 77: ......