Installation Manual
7
Installation
Read completely, then follow step by step.
Installation
Selection of the best location
CAUTION
: In case that the unit is installed near the sea, the installation parts may be corrod-
ed by salt. The installation parts (and the unit) should be taken by appropriate anti-
corrosion measures.
• Do not have any heat or steam near the unit.
• Select a place where there are no obstacles in front of the unit.
• Make sure that condensation drainage can be conveniently routed away.
• Do not install near a doorway.
• Ensure that the space around the left and right of the unit is more than 50cm. The unit should be installed as high on the
wall as possible, allowing a minimum of 10cm from ceiling.
• Use a stud finder to locate studs to prevent unnecessary damage to the wall.
More than 10cm
More than 50cm
More than 2m
More than 50cm