Installation Manual
13
Installation
Remote control
box body
Cord clamp
(accessory)
Lever carefully
the box open
using a screw
driver, etc.
Front case
The lo
wer par
t
Face of wall
Under plate
Screw (accessory)
• Separate the under plate from Remote
control box.
• Attach insulator to under plate.
• Fix the under plate on the wall
• Fix the cord clamps on the wall by ø 3 tapping screws (accessory).
• Fix the remote control cord.
WIRED REMOTE CONTROL INSTALLATION
DISASSEMBLING
ELECTRICAL WIRING
Wire and make sure that teminal
numbers are matched on unit side and
remote control side.
The maximum length of the cord is 100m.
If the length of the cord exceeds 50m,
use a wire size greater than 0.5mm
2
.
Remote control
(Main board)
CN REMO
• Although the room themperature sensor is in the indoor unit, the remote control should be installed in such
places away from direct sunlight and high humidity.
Installation of the remote control
• Select places that are not splashed with water.
• Select control position after receiving customer approval.
• The room temperature sensor is built in the indoor unit.
• This remote control equipped with liquid crystal display. If this position is higher or lower, display is difficult to
see.(The standard height is 1.2 ~1.5m high)
Routing of the remote control cord
• Keep the remote control cord away from the refrigerant piping and the drain piping.
• To protect the remote control cord from electrical noise, place the cord at least 5cm away from other power
cables (audio equipment. television set, etc.)
• If the remote control cord is secured to the wall, provide a trap at the top of the cord to prevent water droplets
from running.
CAUTION : Use the wireless remote control with the wired.
If you want to use wireless alone, you should do following process.
1) Do auto addressing in connecting the wired.
2) After compelting auto addressing, turn off the power and disconnect the wired.
Installation of Remote Control