How to Set E.S.P?
Note: 1. The above table shows the correlation between the air rates and E.S.P.
Setting Value
70
-
-
-
-
-
-
-
-
-
80
4.0
-
-
-
-
-
-
-
-
90
12.1
6.9
4.13
-
-
-
-
-
-
100
17.0
15.5
11.01
6.2
4.2
-
-
-
-
110
21.4
19.6
17.53
14.0
11.6
6.6
-
-
-
120
25.8
24.0
21.8
19.8
17.9
14.6
12.1
-
-
130
30.0
28.5
26.93
25.3
23.4
21.8
18.1
14.6
11.3
140
36.0
32.1
30.41
29.0
27.4
25.9
21.6
17.8
14.5
143
37.5
33.9
32.1
30.7
28.8
27.2
23.0
20.1
16.8
150
41.0
38.0
36.0
34.5
32.1
30.1
26.3
22.4
18.2
160
42.4
41.6
38.2
36.1
35
34.6
31.1
26.8
23.3
5(50)
6(60)
7(70)
8(80)
9(90)
10(100)
12(120)
14(140)
16(160)
Static Pressure(mmAq(Pa))
JRNU28GBGA4, JRNU36GBGA4, JRNU42GBGA4, JRNU48GBGA4
Setting Value
91
46.5
43.7
38.2
31.3
23.2
14.0
9.0
3.7
-
-
-
96
49.9
46.1
43.0
33.5
31.1
18.4
13.7
9.0
2.6
-
-
101
52.1
50.2
47.9
39.5
37.4
27.3
25.2
17.8
8.9
6.1
-
106
51.4
51.2
50.4
44.4
43.1
33.3
32.1
28.9
21.0
17.9
8.3
111
53.6
53.7
52.9
49.9
48.3
40.6
40.2
32.8
31.5
27.2
17.5
116
55.7
50.8
44.8
42.6
40.1
37.6
32.5
27.6
121
52.2
50.8
50.3
45.7
44.6
38.8
32.2
126
54.4
51.2
50.4
46.0
43.5
5(50)
6(60)
8(80)
10(100) 12(120) 14(140) 15(150) 16(160) 17(170) 18(180) 20(200)
Static Pressure(mmAq(Pa))
JRNU54GBRA4
(Unit: CMM)
-
-
-
-
-
-
-
-
-
-
-
-
-
JRNU76GB8A4, JRNU96GB8A4
(Unit: CMM)
(Unit: CMM)
Setting
Value
Static Pressure(mmAq(Pa))
3(29)
4(39)
5(49)
6(59)
9(88)
12(118) 15(147) 18(177) 20(196) 22(216) 23(226) 25(245)
50
40.3
36.2
-
-
-
-
-
-
-
-
-
-
55
48.8
44.2
36.4
-
-
-
-
-
-
-
-
-
60
54.9
50.2
49.7
45
-
-
-
-
-
-
-
-
65
62.6
60.4
55.1
52.9
-
-
-
-
-
-
-
-
70
67.9
64.5
62.1
60.7
47.1
-
-
-
-
-
-
-
75
75.5
72.2
69
68.5
56.9
44.7
-
-
-
-
-
-
80
82.6
80.9
76.6
75.4
69.7
55.2
-
-
-
-
-
-
85
88.8
85.9
82
81.6
78.6
67.4
55.9
-
-
-
-
-
91
94.7
93
90.4
90.2
87.1
78.9
67.6
54.2
-
-
-
-
95
-
-
-
-
-
86.1
77
66.4
50.6
30
-
-
100
-
-
-
-
-
88.3
84.9
75.9
69.5
60.8
43.1
-
105
-
-
-
-
-
88.3
84.9
81.1
77.4
72
67.9
51.3
Note: 1. The above table shows the correlation between the air rates and E.S.P.
2. Make sure to check and adjust E.S.P (external static pressure) value after the installa-
tion of the product. Otherwise, there is a risk of weak cooling/heating and condensed
water discharge/drop.